| 2018-12-18 08:26:39 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18081039 |
| | 2ND REVIEW: DECEMBER 14, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18081039 |
| | W. P. B. FOUN.: 18080583 |
| | ADD: 300 PALM BEACH LAKES BLVD. |
| | CONT: DPR CONSTRUCTION A GENERAL PARTNERSHIP |
| | TEL: 561-718-2367 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. NOV. 15/2018 |
| | ACTION: DENIED |
| | |
| | 1) OK |
| | |
| | 2A) OK |
| | |
| | 2B) PLEASE NOTE THAT ENERGY COMPLIANCE FORMS WERE NOT |
| | PART OF THIS SUBMISSION. SHOW COMPLIANCE WITH THE 2017 |
| | FBC-ENERGY CODE, SUBMIT AN ENERGY COMPLIANCE REPORT IN |
| | COMPLIANCE WITH EITHER C101.2, C101.5.1 AND CC401.2. |
| | PARTIALLY ADDRESSED: |
| | MECHANICAL AND ELECTRICAL COM CHECKS WERE PROVIDED. |
| | ADDITIONALLY, THERE SHOULD BE COMCHECK FOR THERMAL |
| | ENVELOPE. |
| | PLEASE PROVIDE, OR INDICATE IN RESPONSE WHERE THERMAL |
| | COMPLIANCE IS PROVIDED. |
| | |
| | |
| | 2C) TUES. NOV. 20/18 NEW COMMENT. PLEASE NOTE MISSING |
| | FROM THE FILE FOLDER, THE PLANS INDICATE THE BUILDING |
| | IS TO BE FIRE SPRINKLERED BUT THERE IS NO HYDRAULIC |
| | CALCULATIONS FOR THE FLOW RATE FROM THE NEAREST FIRE |
| | HYDRANT. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | FIRE HYDRANT/WATER SUPPLY/ HYDRAULIC CALCULATIONS |
| | THE HYDRAULIC CALCULATIONS ARE THE BASES FOR THE SIZING |
| | OF THE SYSTEM. |
| | NOT ADDRESSED: |
| | I COULD NOT FIND THE CALCULATIONS IN THE SUPPORTING |
| | DOCUMENTS. |
| | PLEASE UPLOAD INTO SUPPORTING DOCUMENTS OR INDICATE |
| | WHERE INFORMATION WAS ADDED IN PLANS. |
| | |
| | 3) OK |
| | |
| | 4) OK |
| | |
| | 5) OK |
| | |
| | 6) OK |
| | |
| | 7) OK |
| | |
| | 8) OK |
| | |
| | 9) SHEET 002-G-001 INDEX: |
| | 9A) OK |
| | |
| | 9B) OK |
| | |
| | 9C) SEE COMMENT 12B |
| | |
| | 10) SHEET 057-A-001 LIFE SAFETY PLAN LEVEL 01 & |
| | 063-A-101FIRST FLOOR PLAN: |
| | |
| | 10A) OK |
| | ADDITIONAL COMMENT: |
| | IT WAS ESTABLISHED THAT A 2-HOUR SEPARATION BETWEEN S-2 |
| | AND BUSINESS. |
| | HOW IS SECTION OF WALL BETWEEN GARAGE AND BANK OF |
| | BATHROOMS RATED AT 1 HOUR ON SHEET A-001? |
| | |
| | 10B) OK |
| | |
| | 10C) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL |
| | PARKING FOR ALL FLOORS SHOWS OPEN EXIT STAIRS FOR THE |
| | UPPER AND LOWER FLOOR LEVELS FOR ALL FLOORS. PLEASE |
| | NOTE IT WILL DEPEND ON IF THE PARKING GARAGE IS OPEN OR |
| | ENCLOSED IF THE STAIRWELLS WILL NEED TO COMPLY WITH |
| | CHAPTER 10. SEE 406.5.7. |
| | ADDITIONAL COMMENT: |
| | I SEE ADEQUATE INFORMATION THAT THE GARAGE IS OPEN |
| | EXEPT FOR THE AREA ON 1ST FLOOR WHERE THERE ARE A BANK |
| | OF ROOMS 133, 134, 135 AND OTHER ROOMS THAT ENCLOSE |
| | THIS AREA ON THREE SIDES. THIS AREA DOES NOT MEET THE |
| | CRITERIA FOR OPENINGS DISTRUBUTED OVER TWO SIDES OR |
| | ALONG 40% OF PERIMETER. |
| | HOW WILL THIS AREA BE VENTILATED? |
| | |
| | 10D) THE FIRST FLOOR PLAN INDICATES A ONE HOUR |
| | ENCLOSURE FOR MEDICAL GAS USE. PLEASE PROVIDE THE TYPES |
| | OF GASSES TO BE ENCLOSED IN THIS ROOM, QUANTITIES OF |
| | GAS WITHIN EACH TANK, QUANTITIES OF EACH TYPE OF GAS IN |
| | TANKS (IN CUBIC FEET) AND THE ACCOMPANYING MSDS SHEETS. |
| | 2017 FBC-B TABLE 307.1(1). |
| | PLEASE ALSO SHOW HOW THE TANKS ARE GOING TO BE STORED, |
| | AND HOW THEY WILL BE SECURED WHILE IN SERVICE. |
| | 107.2.2.1. |
| | MONDAY NOV. 19/18 COMMENT. 451.3.15 MEDICAL GAS. IF |
| | THERE IS A PIPED MEDICAL GAS INSTALLATION IN THE ASC, |
| | IT SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 99 HEALTH |
| | CARE FACILITIES CODE. |
| | ADDITIONAL COMMENT: |
| | [FBC TABLE 307.1(1)]BASED ON THE AMOUNTS OF FLAMABLE |
| | MATERIAL BEING STORED IT WOULD BE CONSIDERED H-2. |
| | [FBC TABLE 508.4]H-2 REQUIRES 3-HOUR SEPARATION FROM |
| | S-2. |
| | PROVIDE DETAIL FOR 3-HOUR ASSEMBLY AT H-2 STORAGE. |
| | |
| | [F] 414.3 VENTILATION. ROOMS, AREAS OR SPACES IN WHICH |
| | EXPLOSIVE, CORROSIVE, COMBUSTIBLE, FLAMMABLE OR HIGHLY |
| | TOXIC |
| | DUSTS, MISTS, FUMES, VAPORS OR GASES ARE OR MAY BE |
| | EMITTED |
| | DUE TO THE PROCESSING, USE, HANDLING OR STORAGE OF |
| | MATERIALS |
| | SHALL BE MECHANICALLY VENTILATED WHERE REQUIRED BY THIS |
| | CODE, |
| | THE FLORIDA FIRE PREVENTION CODE OR THE FLORIDA |
| | BUILDING |
| | CODE, MECHANICAL. |
| | |
| | 10E) OK |
| | |
| | 10F) OK |
| | |
| | 11) ELEVATORS: |
| | 11A) OK |
| | |
| | 11B) OK |
| | |
| | 11C)(1) OK |
| | |
| | 11C)(2) OK |
| | |
| | 11D) OK |
| | |
| | 11E) OK (SEE COMMENT 10A ADDITIONAL COMMENT) |
| | |
| | 12) THE 2ND FLOOR PLANS, 058-A-002 LIFE SAFETY PLAN |
| | LEVEL 02 & 064-A-102: |
| | |
| | 12A) OK |
| | |
| | 12B) PARTIALLY ADDRESSED-SEE ADDITIONAL BELOW |
| | [FBC A502.5]VERTICAL CLEARANCE. PARKING SPACES FOR VANS |
| | AND ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM |
| | SHALL PROVIDE A VERTICAL CLEARANCE OF 98 INCHES. |
| | PLEASE PROVIDE DIMENSION FOR VERTICAL CLEARANCE AT |
| | ENTRY TO ALLOW FOR VAN ACCESSIBLE PARKING (98 INCH |
| | CLEARANCE) VERTICAL CLEARANCE BE PROVIDED IF IT IS |
| | LOCATED IN THE PARKING GARAGE? |
| | |
| | |
| | 12C)(1) OK |
| | 12C)(2) ) OK |
| | |
| | |
| | 12D) OK |
| | |
| | 12E) OK |
| | |
| | 12F) OK |
| | |
| | 12G) OK |
| | |
| | 12H) OK |
| | |
| | 12I) OK |
| | |
| | 13) SHEET 065-A-103 & 059-A-003: |
| | |
| | 13A) OK |
| | |
| | 13B) OK |
| | |
| | 13H) OK |
| | |
| | 13I) SEE 13B |
| | |
| | TUES. NOV. 20/18. |
| | |
| | 14) 060-A-004 LIFE SAFETY PLAN & 066-A-104 FOURTH FLOOR |
| | PLAN: |
| | |
| | 14A) ROOM 434 PATIENT TOILET DOOR SWINGS OUT INTO THE |
| | CORRIDOR, PLEASE SHOW COMPLIANCE WITH 2017 FBC-B |
| | 451.3.4.1. NO DOORS SHALL SWING INTO THE CORRIDOR |
| | EXCEPT THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR |
| | ELECTRICAL ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH |
| | THE DOORS IN THE CLOSED POSITION. |
| | ADDITIONAL COMMENT: |
| | THE RESPONSE DOESN?T ADDRESS 451.3.4.1 THAT STATES NO |
| | DOOR SHALL SWING INTO CORRIDOR. |
| | PLEASE PROVIDE CODE SECTION FOR EXEMPTION OR ADJUST |
| | DOOR SWING ACCORDINGLY. |
| | |
| | 14B) OK |
| | |
| | 14C) OK |
| | |
| | 14D) OK |
| | |
| | 14E) OK |
| | |
| | 14F) OK |
| | |
| | 15) 070-A-108 ROOF PLAN: |
| | |
| | 15A-15B) OK |
| | |
| | 16) 071-A-201, 072-A-202 & 073-A-203 EXTERIOR |
| | ELEVATIONS: |
| | |
| | 16A) PROVISO: ALUMINUM COMPOSITE METAL PANEL SYSTEM |
| | WILL BE ADDED TO DEFERRED SUBMITTAL LIST. |
| | |
| | 16B) OK |
| | |
| | 16C) OK |
| | |
| | 16C)(1) OK |
| | |
| | 16C)(2) OK |
| | |
| | 16D) PROVISO: EXTERIOR SUNSHADE SYSTEM WILL BE ADDED TO |
| | DEFERRED SUBMITTAL LIST. |
| | |
| | 17) OK |
| | |
| | 18) OK |
| | |
| | 19) SHEET 011-S-002: |
| | 19A) OK |
| | |
| | 19B) OK |
| | |
| | 20A) PROVISO: DEFERRED SUBMITTAL LIST FROM G-001 WILL |
| | BE ADDED TO PROVISOS. |
| | |
| | 20B) OK |
| | |
| | 20C) OK |
| | |
| | 20E) OK |
| | |
| | 20F) OK |
| | |
| | 20G) OK |
| | |
| | 21) OK |
| | |
| | NEW COMMENTS (2ND REVIEW): |
| | |
| | 22) CIVIL AND LANDSCAPE PLANS THAT ARE MULTI FILE IN |
| | THE SUPPORTING DOCUMENTS SHOULD BE MOVED TO DRAWING |
| | FOLDER. EACH DRAWING SHOULD BE DIGITALLY SIGNED AND |
| | [FBC 107.2.1]PLACE A DIGITALLY CREATED IMAGE OF YOUR |
| | SEAL AND THE FOLLOWING SENTENCES WHERE AN ORIGINAL |
| | SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING |
| | PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN |
| | BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE |
| | AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON |
| | THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK. |
| | THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY |
| | [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP |
| | SHOWN USING A DIGITAL SIGNATURE. |
| | |
| | PROVISO: |
| | EXTERIOR DOORS AND MULLIONS |
| | WINDOWS AND MULLIONS |
| | PANEL WALLS, STOREFRONT, CURTAIN WALLS AND LOUVERS |
| | EXTERIOR FINISHES (STUCCO SYSTEM) |
| | ALUMINUM METAL COMPOSITE PANEL SYSTEM |
| | ROOFING PRODUCTS AND ASSEMBLIES |
| | FIRE SUPPRRESSION SYSTEM |
| | FIRE ALARM SYSTEM |
| | X-RAY AND PHYSICIST SHEILDING REPORT |
| | EXTERIOR SUNSHADE SYSTEM |
| | EXTERIOR SIGNAGE |
| | FIRE STOPPING |
| | HVAC SYSTEM |
| | PLUMBING SYSTEM |
| | METAL GUARD RAILS AND HANDRAILS |
| | ART IN PUBLIC PLACES |
| | IRRIGATION |
| | DUMPSTER ENCLOSURE |
| | |
| | |