| 2018-10-25 12:14:47 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | FUEL GAS COMMENTS: |
| | 1. PLEASE LIST THE SIZING TABLE USED IN SIZING SYSTEM. |
| | PER FBC FG TABLE 40204(1)-(37) |
| | 2. SHT P-902 THERE IS A NOTE ON THE PLAN THAT STATES A |
| | SYSTEM PRESSURE OF 5PSI THE GAS ISOMETRIC SHOWS 0.5PSI |
| | SHT P-802 DETAILS #2+4 ALSO SHOW 5PSI ON ONE AND 0.5PSI |
| | ON THE OTHER PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 3. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| | GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 |
| | THROUGH G2439. |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND |
| | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1 |
| | 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. |
| | G2413.4.1, G2413.4.2. |
| | 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | 7. SHT P-902 THE GAS ISOMETRIC SHOWS 31/2? PIPE I DON?T |
| | THINK THAT THEY MAKE GAS PIING IN THAT SIZE PLEASE SIZE |
| | THE SYSTEM PER THE SIZING TABLES IF THEY DO MAKE GAS |
| | PIPING IN 31/2 PLEASE PROVIDE MANUFACTURE |
| | SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1 |
| | 8. SHT P-802 DETAIL #2 SHOWS 1? TO THE WATER HEATERS |
| | THE GAS ISOMETRIC SHOWS 21/2? PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 9. SHT P-802 DETAIL #4 SHOWS AN EMERGENCY GENERATOR THE |
| | ISOMETRIC DOES NOT SHOW A GENERATOR PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |