| 2018-09-14 16:58:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | FIRE CODE REFERENCES: SHEET G 001 - THERE ARE CONFLICTS |
| | WITH THE CURRENT EDTIONS OF THE FIRE CODE. THE 2017 |
| | FLORIDA FIRE PREVENTION CODE IS CORRECT; HOWEVER, THE |
| | CODE EDITIONS UNDER THE FFPC ARE INCORRECT. THEY ARE |
| | TOO NUMEROUS TO INDICATE HERE. |
| | |
| | PLEASE REVIEW THE REFERENCED NFPA EDITIOSN UNDER THE |
| | CURRENT FFPC AND CORRECT AND ENSURE COMPLIANCE WITH |
| | THOSE NEW REFERENCES. |
| | |
| | |
| | |
| | |
| | 1) SHEET A 001 - THERE IS A COMMENT INDICATED REGARDING |
| | UNPROTECTED OPENINGS IN AN 1 HOUR RATED WALL WITH A |
| | BUILDING CODE REFERENCE. |
| | |
| | THERE IS NO SUCH REFERENCE INDICATED FROM THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | |
| | PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE |
| | FFPC REFERCE OR CORRECT. |
| | |
| | |
| | |
| | 2) SHEET A002 - THERE IS A COMMENT INDICATED REGARDING |
| | UNPROTECTED OPENINGS IN AN 1 HOUR RATED WALL, WITH A |
| | BUILDING CODE REFERENCE. |
| | |
| | THERE IS NO SUCH REFERENCE INDICATED FROM THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | |
| | PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE |
| | FFPC REFERCE OR CORRECT. |
| | |
| | |
| | |
| | 3) A SHEETS - A PARKING GARAGE IS INDICATED; HOWEVER, |
| | THERE ARE INDICATIONS IF IT IS OPEN OR CLOSED. |
| | |
| | PER NFPA 101, CHAPTER 42 AND 88A |
| | |
| | 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES. |
| | |
| | 42.8.1.3 OPEN PARKING STRUCTURES. OPEN PARKING |
| | STRUCTURES SHALL |
| | COMPLY WITH 42.8.1.3.1 THROUGH 42.8.1.3.3. |
| | 42.8.1.3.1 EACH PARKING LEVEL SHALL HAVE WALL OPENINGS |
| | OPEN TO THE |
| | ATMOSPHERE FOR AN AREA OF NOT LESS THAN 1.4 FT2 FOR |
| | EACH LINEAR FOOT |
| | (0.4 M2 FOR EACH LINEAR METER) OF ITS EXTERIOR |
| | PERIMETER. [88A:5.5.1] |
| | 42.8.1.3.2 THE OPENINGS ADDRESSED IN 42.8.1.3.1 SHALL |
| | BE |
| | DISTRIBUTED OVER 40 PERCENT OF THE BUILDING PERIMETER |
| | OR UNIFORMLY |
| | OVER TWO OPPOSING SIDES. [88A: 5.5.2] |
| | 42.8.1.3.3 INTERIOR WALL LINES AND COLUMN LINES SHALL |
| | BE AT LEAST 20 |
| | PERCENT OPEN, WITH OPENINGS DISTRIBUTED TO PROVIDE |
| | VENTILATION. |
| | [88A: 5.5.3] |
| | |
| | PLEASE PROVIDE APPLICABLE GARAGELASSIFICATION AND |
| | SPECIFIC MATHMATICAL DETAILS SHOWIN GCOMPLIANCE THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | 4) A SHEETS - STAIRWELLS IN THE GARAGE MAY BE REQUIRED |
| | TO BE PROTECTED IF COMPLIANCE WITH OPEN GARAGE IS NOT |
| | MET. |
| | |
| | |
| | |
| | 5) SHEET A 004 - THERE APPEARS TO BE A GLASS STRUCTURE |
| | WITHIN A FIRE RATED WALL IN THE AREA OF SC 1 & 2 WITH A |
| | COMMENT THAT IT IS NOT REQUIRED TO BE RATED. |
| | |
| | THERE IS NO SUCH REFERENCE INDICATED IN THE FLORIDA |
| | FIRE PREVENTION CODE TO ALLOW FOR THIS NON-RATED |
| | OPENING. |
| | |
| | PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE |
| | FFPC REFERCE OR CORRECT. |
| | |
| | |
| | |
| | 6) FP 201 - THERE ARE NO FIRE SPRINKLERS SHOWN |
| | THROUGHOUT THE BUILDING. THE BUILDING CODE REQUIRES A |
| | AUTOMATIC FIRE SPRINKLER SYSTEM. |
| | |
| | [F]903.2.11.3 BUILDINGS THREE STORIES OR MORE IN |
| | HEIGHT. |
| | |
| | ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN |
| | HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| | 903.1. |
| | |
| | |
| | |
| | 7) ALL STRUCTURAL SHEETS - THERE ARE INDICATIONS OF |
| | EACH WALL ON EACH FLOOR SEPARATING THE GARAGE AND |
| | BUSINESS OCCUPANCIES AS BEING 1 HOUR. |
| | |
| | PER NFPA 101, CHAPTER 38 NEW BUSINESS OCCUPANCIES |
| | |
| | 38.1.3.2 COMBINED BUSINESS OCCUPANCIES AND PARKING |
| | STRUCTURES. |
| | 38.1.3.2.1 THE FIRE BARRIER SEPARATING PARKING |
| | STRUCTURES FROM A BUILDING |
| | CLASSIFIED AS A BUSINESS OCCUPANCY SHALL BE A FIRE |
| | BARRIER HAVING A |
| | MINIMUM 2-HOUR FIRE RESISTANCE RATING. |
| | 38.1.3.2.2 OPENINGS IN THE FIRE BARRIER REQUIRED BY |
| | 38.1.3.2.1 SHALL NOT |
| | BE REQUIRED TO BE PROTECTED WITH FIRE PROTECTION?RATED |
| | OPENING |
| | PROTECTIVES IN ENCLOSED PARKING STRUCTURES THAT ARE |
| | PROTECTED THROUGHOUT |
| | BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | IN ACCORDANCE |
| | WITH 9.7.1.1(1), OR IN OPEN PARKING STRUCTURES, |
| | PROVIDED THAT ALL OF THE |
| | FOLLOWING CONDITIONS ARE MET: |
| | (1) THE OPENINGS DO NOT EXCEED 25 PERCENT OF THE AREA |
| | OF THE FIRE |
| | BARRIER IN WHICH THEY ARE LOCATED. |
| | (2) THE OPENINGS ARE USED AS A PUBLIC ENTRANCE AND FOR |
| | ASSOCIATED |
| | SIDELIGHT FUNCTIONS. |
| | (3) THE BUILDING CONTAINING THE BUSINESS OCCUPANCY IS |
| | PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER |
| | SYSTEM IN ACCORDANCE WITH 9.7.1.1(1). |
| | (4) *MEANS ARE PROVIDED TO PREVENT SPILLED FUEL FROM |
| | ACCUMULATING |
| | ADJACENT TO THE OPENINGS AND ENTERING THE BUILDING. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERNCES |
| | |
| | 8) SHEET E 001 - THERE ARE INDICATIONS/SYMBOLS UNDER |
| | THE FIRE ALARM SECTION LEGEND; HOWEVER, THERE ARE NO |
| | SYMBOLS INDICATED ON ANY ELEVTRICAL SHEETS NOT |
| | INDICATIONS THAT FIRE ALARM DRAWINGS SHALL BE UNDER |
| | SPEARATE SHOP DRAWINGS. |
| | |
| | PER NFPA 101, CHAPOTER 38, NEW BUSINESS OCCUPANCIES |
| | |
| | 38.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 38.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE |
| | WITH |
| | SECTION 9.6 SHALL BE PROVIDED IN ALL BUSINESS |
| | OCCUPANCIES |
| | WHERE ANY ONE OF THE FOLLOWING CONDITIONS EXISTS: |
| | (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT. |
| | (2) THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS |
| | ABOVE |
| | OR BELOW THE LEVEL OF EXIT DISCHARGE. |
| | (3) THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL |
| | OCCUPANTS. |
| | 38.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE |
| | ALARM SYSTEM |
| | SHALL BE BY ANY ONE OF THE FOLLOWING MEANS: |
| | (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1) |
| | (2) APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN |
| | ACCORDANCE |
| | WITH 9.6.2.1(2) THAT PROVIDES PROTECTION THROUGHOUT THE |
| | BUILDING AND THE PROVISION OF 9.6.2.6 SHALL APPLY. |
| | (3) APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | 9.6.2.1(3) THAT PROVIDES PROTECTION THROUGHOUT THE |
| | BUILDING AND THE PROVISION OF 9.6.2.6 SHALL APPLY. |
| | 38.3.4.3 OCCUPANT NOTIFICATION. DURING ALL TIMES THAT |
| | THE |
| | BUILDING IS OCCUPIED (SEE 7.2.1.1.3), THE REQUIRED FIRE |
| | ALARM |
| | SYSTEM, ONCE INITIATED, SHALL PERFORM ONE OF THE |
| | FOLLOWING |
| | FUNCTIONS: |
| | (1) IT SHALL ACTIVATE A GENERAL ALARM IN ACCORDANCE |
| | WITH 9.6.3. |
| | (2) A POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH |
| | 9.6.3.4 |
| | SHALL BE PERMITTED. |
| | (5) PHYSICAL MEANS ARE PROVIDED TO PREVENT VEHICLES |
| | FROM BEING |
| | PARKED OR DRIVEN WITHIN 10 FT (3050 MM) OF THE |
| | OPENINGS. |
| | (6) THE OPENINGS ARE PROTECTED AS A SMOKE PARTITION IN |
| | ACCORDANCE |
| | WITH SECTION 8.4, WITH NO MINIMUM FIRE PROTECTION |
| | RATING REQUIRED. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 9) LIFE SAFETY SHEETS - THERE ARE INDICATIONS THAT EXIT |
| | ACCESS CORRIDORS ON ANY FLOOR LEVEL ARE NOT PROTECTED |
| | BY 1 HOUR FIRE WALLS |
| | |
| | PER NFPA 101 - |
| | |
| | 38.3.6 CORRIDORS. |
| | 38.3.6.1* WHERE ACCESS TO EXITS IS PROVIDED BY |
| | CORRIDORS, SUCH |
| | CORRIDORS SHALL BE SEPARATED FROM USE AREAS BY FIRE |
| | BARRIERS IN |
| | ACCORDANCE WITH SECTION 8.3 HAVING A MINIMUM 1-HOUR |
| | FIRE |
| | RESISTANCE RATING, UNLESS ONE OF THE FOLLOWING |
| | CONDITIONS EXISTS: |
| | (1) *WHERE EXITS ARE AVAILABLE FROM AN OPEN FLOOR AREA |
| | (2) *WITHIN A SPACE OCCUPIED BY A SINGLE TENANT |
| | (3) WITHIN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | 9.7.1.1(1) |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERNECES |
| | |
| | |
| | |
| | 10) LIFE SAFETY SHEETS - IN REFERNCE TO # 9 ABOVE THE |
| | DOOR SCHEDULE DOES NOT INDICATED FIRE DOOR RATINGS IN |
| | APPLICABLE CORRIDORS. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 11) SHEET E 001- THERE IS AN INDICATION OF A GENERATOR |
| | |
| | THE GENERATOR INSTALLATION SHALL BE UNDER SEPARATE SHOP |
| | DRAWINGS AND COMPLY WITH NFPA 37 AND NFPA 110 IF |
| | SUPPORTING THE LIFE SAFETY SYSTEMS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | 12) THERE ARE NUMEROUS INDICATION OF SMOKE BARRIERS AND |
| | SMOKE PARTITIONS, HOWEVER, THERE IS NO NARRATIVE |
| | COMPLYING WITH NFPA 1 |
| | |
| | 10.14.3.4.2 LIFE SAFETY NARRATIVE. A LIFE SAFETY |
| | NARRATIVE SHALL BE |
| | PROVIDED DESCRIBING THE FOLLOWING: |
| | (1) BUILDING OCCUPANCY, CONSTRUCTION TYPE, AND INTENDED |
| | USES AND EVENTS |
| | (2) BUILDING AREA AND POPULATION CAPACITY OF THE |
| | PROPOSED FACILITY |
| | (3) PRINCIPAL FIRE AND LIFE SAFETY FEATURES/STRATEGIES |
| | FOR THE BUILDING, |
| | INCLUDING THE FOLLOWING: |
| | (A) SPRINKLER PROTECTION |
| | (B) SMOKE CONTROL/PROTECTION |
| | (C) FIRE ALARM - VISUAL AND AUDIBLE |
| | (D) PA SYSTEM |
| | (E) EMERGENCY POWER AND LIGHTING |
| | (F) PROVISIONS FOR PATRONS WITH DISABILITIES |
| | (G) FIRE DEPARTMENT ACCESS |
| | (H) FIRE/EMERGENCY COMMAND CENTER |
| | (4) EXTERIOR CONSTRUCTION DESIGN PARAMETERS |
| | USED/APPLIED |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | |
| | 13) SHEET A 003, A 104 & A 611 - THERE IS AN INDICATION |
| | OF AN ELEVATOR LOBBY ON THE 3RD AND 4TH FLOOR. THE |
| | HARDWARE SET FOR THESE LOBBY DOORS AND OTHER DOORS |
| | LEADDING TO AN EXIT COULD NOT BE FOUND TO ENSURE |
| | COMPLIANCE WITH THE BELOW CODE. |
| | |
| | 7.4.1.6 ELEVATOR LANDING AND LOBBY EXIT ACCESS. |
| | 7.4.1.6.1 EACH ELEVATOR LANDING AND LOBBY SHALL HAVE |
| | ACCESS TO AT |
| | LEAST ONE EXIT. |
| | 7.4.1.6.2 THE ELEVATOR LANDING AND LOBBY EXIT ACCESS |
| | REQUIRED BY |
| | 7.4.1.6.1 SHALL NOT REQUIRE THE USE OF A KEY, A TOOL, |
| | SPECIAL |
| | KNOWLEDGE, OR SPECIAL EFFORT, UNLESS PERMITTED BY |
| | 7.4.1.6.3. |
| | 7.4.1.6.3 DOORS SEPARATING THE ELEVATOR LOBBY FROM THE |
| | EXIT ACCESS |
| | REQUIRED BY 7.4.1.6.1 SHALL BE PERMITTED TO BE |
| | ELECTRONICALLY LOCKED |
| | IN ACCORDANCE WITH 7.2.1.6.3. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 14) SHEET 611 - THE HARDWARE SET IDENTIFICATION TABLE |
| | COULD NOT BE EASILY LOCATED OR FOUND. |
| | |
| | PLEASE CORRECT OR PROVIDE THE SHEET NUMBER FOR |
| | VERIFICATION PURPOSES. |
| | |
| | |
| | |
| | 15) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |