| 2018-10-04 15:57:24 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| | EC C405.6.1 |
| | 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 4. PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED |
| | PER NEC 517.13 . |
| | 5. RISER DIAGRAM DOES NOT SHOW FEEDER WIRE AND CONDUIT |
| | SIZES. THIS INFORMATION IS ONLY PROVIDED FOR A FEW |
| | CIRCUITS IN THE PANEL SCHEDULES. PROVIDE CORRECTION. |
| | WPB FBC 107.2.1; NEC 310.15(B)(16) AND CHAPTER 9 |
| | TABLES. |
| | 6. PANEL 4DPH SHOWS A DEMAND LOAD OF 692550 VA WHICH |
| | EQUALS APPROXIMATELY 834 AMPS. THIS PANEL IS RATED FOR |
| | 800 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36, |
| | 310.15, 215.2 |
| | 7. SHEET E-101 SHOWS FEED FROM GENERATOR GOING DIRECTLY |
| | TO PANEL EDP, BUT THE RISER DIAGRAM SHOWS THE GENERATOR |
| | FEED GOING TO A DUAL PURPOSE DOCKING STATION. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. SHOW LOCATION OF DUAL |
| | PURPOSE DOCKING STATION ON PLAN. PROVIDE SPEC SHEET FOR |
| | THIS PRODUCT. WPB FBC 107.2.1; NEC 110.3 |
| | 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| | CODE. NEC 210.64 |
| | 9. PLAN DOES NOT SHOW THE PANEL BOARD BONDING REQUIRED. |
| | PROVIDE CORRECTION. NEC 517.14 |
| | 10. PLAN DOES NOT SHOW THE GFCI PROTECTION OR |
| | EQUIVALENT FOR HYDROTHERAPY ROOM. PROVIDE CORRECTION. |
| | NEC 517.20 |
| | 11. ROOMS 211 AND 215 SHOW RECEPTACLE OUTLETS WITHIN 6 |
| | FEET OF A SINK THAT ARE NOT GFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.8(B)(5) |
| | 12. PANELS 1P1, E1P1, 1P2, E1P2, 1P3, E1P3, 1P4, AND |
| | E1P4 ARE NOT SHOWN ON RISER DIAGRAM OR IN PANEL |
| | SCHEDULES. WHERE ARE THESE PANELS FED FROM, WHAT IS THE |
| | LOAD, AND IS THIS LOAD INCLUDED IN THE LOAD CALCULATION |
| | FOR THE SERVICE? PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. WPB FBC 107.2.1; NEC 215.2, 215.5, 220 |
| | 13. WOMENS LOCKER ROOM (ROOM 461) AND MENS LOCKER ROOM |
| | (ROOM 464) SHOW RECEPTACLE OUTLETS THAT ARE NOT GFCI |
| | PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(7) |
| | 14. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| | 105.1, 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |