| Plan Review Notes For Permit 18081031 |
| Permit Number |
18081031 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-12-02 16:00:51 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 1901 | | | 3RD REVIEW: DECEMBER 2, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | R402.1 GENERAL (PRESCRIPTIVE). THE BUILDING THERMAL | | | ENVELOPE SHALL MEET THE REQUIREMENTS OF SECTIONS | | | R402.1.1 THROUGH R402.1.5. | | | | | | R402.1.2 INSULATION AND FENESTRATION CRITERIA. THE | | | BUILDING THERMAL ENVELOPE SHALL MEET THE REQUIREMENTS | | | OF TABLE R402.1.2, BASED ON THE CLIMATE ZONE SPECIFIED | | | IN CHAPTER 3. | | | | | | IF FOLLOWING PRESCRIPTIVE THE R VALUES COME FROM TABLE | | | R402.1.2. CEILING R VALUE I9S LISTED AT R-30. | | | SIMULATED PERFORMANCE METHOD ALLOWS FOR LOWER R VALUES | | | SINCE IT TAKES IN MULTIPLE FACTORS AND CALCULATES THE | | | WHOLE ENVELOPE. | | | |
|