| Plan Review Notes For Permit 18081031 |
| Permit Number |
18081031 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-22 08:33:31 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 1901 | | | REVIEWED: APRIL 22, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: | | | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN | | | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF | | | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED | | | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY | | | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. | | | | | | 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE | | | PART OF THE ALTERATION SHALL COMPLY WITH SECTION | | | R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH | | | R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5 | | | ADDITIONS SHALL BE IN ACCORDANCE WITH SECTION R502.1.1, | | | R502.1.2 OR R502.1.3. | | | 1) WHICH METHOD IS BEING USED? IF PERSCRIPTIVE REVIEW | | | R-20 AT CEILING. | | | | | | 103.1.1.2 FBC[RE] IF SIMULATED PROVIDED, PLEASE HAVE | | | THE OWNER SIGN THE ENERGY CALCULATIONS. | | | | | | 2) 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES | | | REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH | | | THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD | | | INDEX AND SMOKE DEVELOPED INDEX. | | | |
|