Plan Review Notes
Plan Review Notes For Permit 18081031
Permit Number 18081031
Review Stop B
Sequence Number 2
Notes
Date Text
2019-04-22 08:33:31****CORRECTIONS****
 W.P.B. PERMIT: 1901
 REVIEWED: APRIL 22, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
  
 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE
 PART OF THE ALTERATION SHALL COMPLY WITH SECTION
 R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH
 R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5
 ADDITIONS SHALL BE IN ACCORDANCE WITH SECTION R502.1.1,
 R502.1.2 OR R502.1.3.
 1) WHICH METHOD IS BEING USED? IF PERSCRIPTIVE REVIEW
 R-20 AT CEILING.
  
 103.1.1.2 FBC[RE] IF SIMULATED PROVIDED, PLEASE HAVE
 THE OWNER SIGN THE ENERGY CALCULATIONS.
  
 2) 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  