| Plan Review Notes For Permit 18080931 |
| Permit Number |
18080931 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-27 10:42:19 | BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- NO CLEAR WHAT TYPE OF SOUND INSULATION IS GOING BE | | | INSTALLED. THERE IS ONE PAGE CALLING FOR SUPER SAM 125 | | | BUT COPIES OF SOUND INSULATION TESTING SUBMITTED IS FOR | | | SAM 90 INSULATION. CLARIFY AS REQUIRED AND PROVIDE TWO | | | COPIES OF TESTING FOR THE FOLLOWING: | | | | | | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE | | | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION | | | (2017). | | | | | | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS | | | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS | | | REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). | | | | | | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS | | | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS | | | REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). | | | | | | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE | | | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | | ACOUSTICAL CEILING. THERE IS NOT SUSPENDED ACOUSTICAL | | | CEILING IN THIS BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|