| Plan Review Notes For Permit 18080928 |
| Permit Number |
18080928 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-12-11 07:24:43 | 12/11/2018 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. SECOND REQUEST, SIGNATURE OF AN ARCHITECT-ENGINEER | | | IS REQUIRED (OR SEAL, OR TITLE BLOCK, OR ALL THREE) ARE | | | NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.001, FLORIDA STATUTE 471.2. | | | 2. SHOWER CONTROL VALVES SHALL BE PRESSURE-BALANCE, | | | THERMOSTATIC-MIXING OR COMBINATION | | | PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A | | | HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME | | | A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET | | | TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN | | | 120?F. | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|