| Notes |
| Date |
Text |
| 2018-08-24 07:28:54 | 8/24/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. GOVERNING CODES HAVE CHANGE SINCE 2004 PLEASE UPDATE | | | PLANS TO REFLECT 2017 FBC 6TH EDITION. | | | 2. SHOWER CONTROL VALVES SHALL BE PRESSURE-BALANCE, | | | THERMOSTATIC-MIXING OR COMBINATION | | | PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A | | | HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME | | | A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET | | | TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN | | | 120?F. | | | 3. SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED (OR | | | SEAL, OR TITLE BLOCK, OR ALL THREE) ARE NOT IN | | | ACCORDANCE WITH FLORIDA | | | ADMINISTRATIVE CODE 61G15-23.001, FLORIDA STATUTE 471. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|