| 2018-10-24 06:39:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN PROVIDED IS NOT SIGNED AS PER LAST PLAN REVIEW |
| | COMMENTS. |
| | ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 2. BLEAKLEY ELECTRIC APPLIED FOR A ELEC-SUB PERMIT BUT |
| | HAS REFERENCED THE MASTER SET OF PLANS (PLANS SUBMITTED |
| | FOR THIS PERMIT). PROVIDE ELECTRICAL PLAN FOR REVIEW, |
| | SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR |
| | SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER. |
| | INDICATE EXISTING CONDUIT SIZE, WIRE SIZE, AND OCP TO |
| | NEW PROPOSED FIRE PUMP FROM EXISITNG FIRE PUMP |
| | CONTROLLER. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1, |
| | 107.3.5 |
| | |
| | 3. INITIAL PERMIT APPLICATION SAID "INSTALLATION OF NEW |
| | FIRE PUMP AND CONTROLLER" NOW CONTRACTOR STATES ONLY |
| | THE FIRE PUMP IS TO BE REPLACED. PROVIDE SPECS FOR |
| | EXISTING FIRE PUMP CONTROLLER, PROVIDE UL/NRTL LISTING |
| | FOR EXISTING FIRE PUMP CONTROLLER AND PROVIDE |
| | DOCUMENTATION THAT SHOWS EXISTING FIRE PUMP CONTROLLER |
| | IS LISTED TO BE USED WITH NEW PROPOSED FIRE PUMP. NEC |
| | 90.7, 110.2, 110.3B |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |