| Date |
Text |
| 2018-09-25 06:33:34 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LICENSED ELECTRICAL CONTRACTOR REQUIRED FOR |
| | DISCONNECTION OF OLD AND INSTALLATION OF NEW FIRE PUMP |
| | AND CONTROLLER, AS PER LAST PLAN REVIEW COMMENTS. |
| | ELECTRICAL CONTRACTOR REQUIRED FBC 105.1, F.S. 489.505 |
| | |
| | 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.2.1, 107.3.5 |
| | |
| | 3. PLAN SHOWS 70PSI, 50HP PUMP BY PEERLESS BUT |
| | SUBMITTAL SAYS 100PSI, 60HP PUMP BY FAIRBANKS. PROVIDE |
| | ACCURATE PLAN AND SUBMITTALS FOR REVIEW. FBC 107.2.1 |
| | |
| | 4. NO UL OR OTHER NRTL LISTING PROVIDED FOR FIRE PUMP. |
| | NO SUBMITTALS PROVIDED FOR FIRE PUMP CONTROLLER. |
| | PROVIDE LISTINGS FOR BOTH NEC 110.3B, FBC 107.2.1 |
| | |
| | 5. VALUE LOW, RAISE VALUE OR VALUE WILL BE SET BY |
| | BUILDING OFFICAL. VALUE TO INCLUDE ALL MATERIALS AND |
| | LABOR.FIRE PUMP, CONTROLLER ETC. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |