| 2018-10-09 10:40:44 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE ENLARGED DETAIL FOR PLUMBING WORK IN THE |
| | KITCHENS WITH DIMENSIONS AND CLARIFY THAT THE SINK AND |
| | WATER HEATER IS BEING RELOCATED IN TYPE B UNITS IN |
| | ORDER TO CLARIFY SCOPE OF PLUMBING WORK. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 2. PROVIDE ENLARGED DETAIL FOR PLUMBING WORK IN THE |
| | BATHROOMS WITH THE DIMENSIONS SHOWING COMPLIANCE WITH |
| | FBC PL 405.3.1 |
| | |
| | 3. PLEASE CLARIFY WILL THE WATER HEATERS IN THE UNITS |
| | BE REPLACED WITH NEW PROVIDE NOTE ON PLAN. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. THE WATER HEATER DETAIL IS SHOWING A RECIRCULATION |
| | SYSTEM THE WATER ISOMETRIC FOR NEW LAUNDRY IS NOT |
| | SHOWING ONE PLEASE CLARIFY ALL PIPING SHALL COMPLY WITH |
| | FBCPL 504.6 PIPING FROM T+P VALVE SHALL DISCHARGE |
| | THROUGH AIR GAP IN THE SAME ROOM. |
| | |
| | 5. THE SANITARY STACK FOR THE WASHING MACHINE STAND |
| | PIPE SHALL BE VENTED FBC PL 910.1 |
| | |
| | 6. THE SHUT OFF VALVES FOR THE STACKABLE WASHING |
| | MACHINE SHALL BE ACCESSIBLE WITHOUT MOVING THE |
| | APPLIANCE. PER FBC PL 606.3 |
| | |
| | 7. PROVIDE ENLARGED FLOOR PLAN. PER WPB AMEND TO FBC |
| | 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 |
| | INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER |
| | ACCEPTABLE MEDIUM. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS |
| | RELATED TO RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE |
| | COMPATIBLE WITH THE ARCHIVE |
| | REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |