| 2018-09-26 16:17:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING EXISTING BUILDING 2017 6TH |
| | EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOAD CALCULATION FOR HOUSE PANEL SHOWS DEMAND |
| | FACTORS FROM NEC 220.82. THESSE DEMAND FACTORS ARE NOT |
| | PERMITTED ON FEDDERS WITH LESS THAN 100 AMPS CAPACITY. |
| | PROVIDE CORRECTION. NEC 220.82 |
| | 2. LOAD CALCULATION FOR PANEL B SHOWS ALL LOADS ADDED |
| | TOGETHER AND THEN DEMAND FACTORS APPLIED. THE AC SHOULD |
| | NOT BE INCLUDED IN THESE DEMAND FACTORS.THE LOAD FOR AC |
| | SHOULD BE AT 100% OF AC, OR 65% OF HEAT, WHICHEVER IS |
| | LARGER. PROVIDE CORRECTION. NEC 220.82 |
| | 3. LOAD CALCULATION FOR PANEL A SHOWS THE AC AT 65%.THE |
| | LOAD FOR AC SHOULD BE AT 100% OF AC, OR 65% OF HEAT, |
| | WHICHEVER IS LARGER. PROVIDE CORRECTION. NEC 220.82 |
| | 4. THIS APPEARS TO BE A LEVEL 2 ALTERATION, ALTHOUGH IT |
| | IS SHOWN AS A REPAIR ON THE PLAN. HOWEVER, ADDITIONAL |
| | AC EQUIPMENT IS BEING ADDED, SO IT WOULD APPEAR THAT IT |
| | SHOULD BE LEVEL 2. PROVIDE CLARIFICATION. FBC EX 504.1 |
| | 5. IF LEVEL 2 ALTERATION, PROVIDE UPGRADE OF ELECTRICAL |
| | IN WORK AREAS TO INCLUDE OUTLET SPACING, AFCI AND GFCI |
| | PROTECTION, AND MINIMUM LIGHTING REQUIREMENTS. FBC EX |
| | 808.3; NEC 210.8, 210.12 |
| | 6. IF EXISTING ELECTRICAL MEETS THE REQUIREMENTS IN |
| | COMMENT 5, SHOW ON PLAN. WPB FBC 107.2.1 |
| | 7. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |