2018-10-30 11:44:561) SHT. M-1 - THE PLANS NOTE THE GAS SYSTEM PRESSURE IS
 11 INCHES WATER COLUMN WITH A PRESSURE DROP OF 6.0 IN.
 WATER COLUMN BUT ON PAGE 5 IN THE REGULATOR
 SPECIFICATIONS YOU HAVE HIGHLIGHTED A 14 INCH WATER
 COLUMN CAPACITY TABLE WITH A 2 INCH WATER COLUMN DROP.
 THIS IS AT THE TOP OF THE PAGE. CLARIFY.
 2) SUPPLY INFORMATION FOR THE SPACING OF THE EXHAUST
 SUPPORTS. ALSO, THE SUPPORT DETAIL ON SHT. M-1 SHOWS A
 PLASTIC ALL THREAD THROUGH THE CLEVIS HANGER. IS THIS
 CORRECT? PLEASE ADVISE.
 3) THE GENERAC SPECS NOTE THE BTU LOAD OF THE GENERATOR
 AS 2,340,000 BTU'S AND THE GAS PLAN SHOWS 2,800,000.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW