| Plan Review Notes For Permit 18080843 |
| Permit Number |
18080843 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-10-30 11:44:56 | 1) SHT. M-1 - THE PLANS NOTE THE GAS SYSTEM PRESSURE IS | | | 11 INCHES WATER COLUMN WITH A PRESSURE DROP OF 6.0 IN. | | | WATER COLUMN BUT ON PAGE 5 IN THE REGULATOR | | | SPECIFICATIONS YOU HAVE HIGHLIGHTED A 14 INCH WATER | | | COLUMN CAPACITY TABLE WITH A 2 INCH WATER COLUMN DROP. | | | THIS IS AT THE TOP OF THE PAGE. CLARIFY. | | | 2) SUPPLY INFORMATION FOR THE SPACING OF THE EXHAUST | | | SUPPORTS. ALSO, THE SUPPORT DETAIL ON SHT. M-1 SHOWS A | | | PLASTIC ALL THREAD THROUGH THE CLEVIS HANGER. IS THIS | | | CORRECT? PLEASE ADVISE. | | | 3) THE GENERAC SPECS NOTE THE BTU LOAD OF THE GENERATOR | | | AS 2,340,000 BTU'S AND THE GAS PLAN SHOWS 2,800,000. | | | CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|