Plan Review Notes
Plan Review Notes For Permit 18080843
Permit Number 18080843
Review Stop G
Sequence Number 1
Notes
Date Text
2018-10-25 11:46:261) TWO DIFFERENT GAS PIPING RISERS HAVE BEEN SUBMITTTED
 FOR THIS WORK. ONE IS FROM ROSADO PROPANE SERVICES AND
 THE OTHER HAS BEEN DONE BY THE ENGINEER OF RECORD.
 SUBMIT TWO COPIES OF THE CORRECT GAS DRAWING TO BE
 SUBMITTED. FBC 107.2.
 2) INDICATE ON THE PLAN THE OPERATING PRESSURE OF THE
 SYSTEM DOWNSTREAM OF THE REGULATOR FOR THE GENERATOR.
 ROSADO PROPANE HAS SUBMITTED A SIZING TABLE FOR 5 PSI
 AND SHT. M-1 SHOWS A PRESSURE OF LESS THAN 2
 PSI.CLARIFY.
 3) SHOW THE PSI OF THE SYSTEM DOWNSTREAM OF THE
 EXISTING GAS METER AND SHOW THE LOCATION OF ANY
 EXISTING GAS REGULATORS ON THE ROSADO PROPANE DRAWING
 IF THAT IS THE DRAWING TO BE USED. FBC 107.2.1.
 4) THE GENERATOR SPECIFICATIONS AND THE DRAWING FROM
 ROSADO PROPANE CALL OUT A 2 INCH GAS SUPPLY LINE TO THE
 GENERATOR AND THE GAS RISER DRAWING ON SHT. M-1 SHOWS A
 1 1/2 INCH GAS SUPPLY LINE. CLARIFY.
 5) SHOW THE DISTANCE OF THE 2ND STAGE REGULATOR TO THE
 GENERATOR ON THE GAS DRAWING TO BE USED. FBC 107.2.1.
 6) THE GAS INFO PAGE FROM ROSADO PROPANE NOTES PIPE
 SIZING FOR NEW GAS LINE IS BASED ON TABLE 402.4 (7) FOR
 A 5 PSI SYSTEM BUT ALSO REFERENCES THE SAME SIZING
 TABLE FOR A LESS THAN 2 PSI SYSTEM. CLARIFY.THIS
 INFORMATION CONFLICTS WITH THE INFORMATION PROVIDED BY
 THE ENGINEER ON SHT. M-1. CLARIFY.
 7) THE GAS DRAWING FROM ROSADO PROPANE SHOWS A 10 PSI
 GAS METER YET DRAWING M-1 SHOWS A LESS THAN 2 PSI
 PRESSURE. CLARIFY.
 8) THE GAS PIPING FROM ROSADO PROPANE SHOWS GALVANIZED
 PIPING TO BE RRUN UNDERGROUND.GALVANIZED PIPING SHALL
 NOT BE USED UNDERGROUND PER FBC-FUEL GAS SEC.404.11,
 404.11.1.
 9) SUBMIT COMBUSTION CALCULATIONS FOR CCOMBUSTION AIR.
 FBC-FUEL GAS SEC.304.1,304.6.2.
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION DETAILS FOR THE NEW EXHAUST PIPE FROM THE
 GENERATOR ( TYPE OF PIPE, TYPE OF SUPPOTS, SUPPORT
 SPACING, ETC.).
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 MINIMUM REQUIRED CLEARANCES AROUND THE GENERATOR. FBC
 107.2.1.
 12) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 IDENTIFY ON THE SPECIFICATION SHEETS WHICH MODEL
 REGULATOR IS BEING INSTALLED AND THE ORIFICE SIZE TO
 ENSURE THE REGULATOR CAN ACCOMMODATE THE BTU LOAD
 THROUGH THE REGULATOR.2017 FGC SEC.410.1, 2017 FBC-RES.
 SEC. G2421.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  