| Date |
Text |
| 2018-09-13 10:46:35 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | FAILED |
| | |
| | 1. FBCR-M1602.3 BALANCED RETURN AIR REQUIRED . |
| | |
| | SHEET M1 THE RETURN AIR SYSTEM IS UNDERSIZED. M1602.3 |
| | EXCEPTION 1. ALLOWS THE FOLLOWING: TRANSFER DUCTS MAY |
| | ACHIEVE THE REQUIREMENT BY INCREASING THE RETURN |
| | TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA (SQUARE |
| | INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR SPACE |
| | IT IS SERVING AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN |
| | AIR BALANCE. |
| | |
| | 2. THIS STRUCTURE IS IDENTIFIED AS A CONTRIBUTING |
| | HISTORIC STRUCTURE ON THE CITY HISTORIC DISTRICT MAPS, |
| | ACCORDINGLY, COMPLIANCE WITH THE FBC ENERGY CODE IS NOT |
| | REQUIRED PER SECTION. R101.4.2.3. PLEASE NOTE THAT |
| | INACCURATE AND INCOMPLETE ENERGY FORMS WERE SUBMITTED |
| | FOR REVIEW. PLEASE ELECT TO REMOVE SUCH FORMS FROM THE |
| | SUBMITTAL AND IF SO PLEASE INDICATE THE APPLICABILITY |
| | OF THE EXEMPTION IN THE PROPERTY INFORMATION OR SCOPE |
| | OF WORK ON SHEET CS-2 OTHERWISE SUPPLY ACCURATE |
| | INFORMATION. IT IS FURTHER NOTED THAT THE WALL & |
| | CEILING SECTIONS SHOWN ON SHEET A-7 INDCATE INSULATION |
| | VALUES THAT APPEAR NOT POSSIBLE TO ACHIEVE GIVEN THE |
| | WALL ASSEMBLY TYPE. THE EQUIPMENT SIZING CALCULATION |
| | WHICH IS NOT REQUIRED LACKS AN ENERGY CALCULATION BASIS |
| | DETERMINING THE COOLING DEMAND EXPRESSED IN BTU'S AND |
| | LACKS THE MODEL AND ANY ACCURATE BASIS TO DETERMINE |
| | COOLING CAPACITY. YOU MAY ELCET TO REMOVE THE SIZING |
| | CALCULATION OR SUBMIT FULL ACCURATE INFORMATION. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |
| | (561) 805-6710 |
| | [email protected] |
| | |