Plan Review Notes
Plan Review Notes For Permit 18080828
Permit Number 18080828
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-08-24 14:21:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAIL ON THE DRAWING OF THE
 ACTUAL LOCATION OF THE DOOR WITHIN THE OCCUPANCY.
  
 PLEASE PROVIDE A MORE DETAILED LOCATION OF THE DOOR ON
 AN ENTIRE FLOOR PLAN OF THE OCCUPANCY.
  
  
  
 2) IF THIS INSTALL IS ON A DOOR IN THE MEANS OF EGRESS
 PLEASE ENSURE THAT IT COMPLIES WITH NFPA 101, CHAPTER
 7, MEANS OF EGRESS
  
  
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS
 EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF
 EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR
 TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE
 DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 COMPLYING WITH ALL OF THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM )
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM)
 OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE
 LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30
 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO
 UNLOCK THE DOOR LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS,
 SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE
 WITH SECTION 7.9.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) DDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL