| Plan Review Notes For Permit 18080815 |
| Permit Number |
18080815 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-01 17:32:43 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | | | | FBC 107. | | | | | | 1. PLEASE CLARIFY THE LOCATION OF PROPOSED SOLAR PANEL | | | SYSTEM. THE PLANS APPEAR TO SHOW CONNECTIONS TO AN | | | EXISTING ROOF DECK AND/OR A NEW ALUMINUM FRAMING SYSTEM | | | DIRECT TO GRADE. | | | | | | | | | | | | AWS D1.1 CLAUSE 3.1 / AWS D1.1 CLAUSE 4.15 | | | | | | 2. IF FIELD WELDING IS GOING TO TAKE PLACE, THE | | | FOLLOWING SPECIFICATIONS WILL BE REQUIRED: | | | | | | A. A WELD PROCEDURE SPECIFICATION; THIS SPECIFICATION | | | IS REQUIRED TO SHOW THE ESSENTIAL VARIABLES USED DURING | | | THE WELDING PROCEDURE AS PER THE REQUIREMENTS OF AWS | | | D1.1. | | | B. A WELDER PERFORMANCE QUALIFICATION TEST RECORD AS | | | PER THE REQUIREMENTS OF AWS D1.1. |
|