| 2018-09-11 14:34:08 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 180814 |
| | PLUMBING COMMENTS: |
| | |
| | 1. RE: PLAN SHEET E-1; SHOW TRAP ON ALL UNDERFLOOR |
| | FIXTURE DRAINS, IE. BATHTUBS AND SHOWERS, UNLESS |
| | FIXTURE IS INTEGRALLY TRAPPED, IE. WATER CLOSETS. FBC |
| | WPB AMEND 107.2.1, FBC RES P3201.2B. CIRCLE SYMBOLS AT |
| | END OF HORIZONTAL PIPING FOR WATER CLOSETS ARE |
| | CONFUSING. PROVIDE VERTICAL EXTENSION AT END OF WATER |
| | CLOSET HORIZONTAL AND PLACE OVAL SYMBOL AT TOP PER FBC |
| | WPB AMEND 107.2.1. |
| | 2. RE: PLAN SHEET E-1; SHOWS SHOWER AND WATER CLOSET |
| | FIXTURE DRAINS SHOWN CONNECTING TO EACH OTHER BEFORE |
| | CONNECTING TO(WET)VENT. MUST CONNECT INDEPENDENTLY TO |
| | VENT FBC RES 3108.1; FIXTURE DRAIN LENGTH TRAP TO VENT |
| | TO BE IN ACCORDANCE WITH FBC RES TABLE P3105.1. |
| | 3. ADD PLUMBING NOTE: SHOWER CONTROL VALVE(S) SHALL BE |
| | PRESSURE BALANCED PB,THERMOSTATIC MIXING (TM) OR |
| | COMBINATION PB/TM VALVE TYPES WITH HIGH TEMPERATURE |
| | LIMITING STOP. 2017 FBC RES 2708.4 |
| | 4. RE: PLAN SHEET E-1; A GAS TANKLESS WATER HEATER IS |
| | SHOWN ON THE PLAN. |
| | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL |
| | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT |
| | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE |
| | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. |
| | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT |
| | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE |
| | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE |
| | FBC-R, SEC. G2404.3. |
| | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL |
| | GAS SEC. 301.3. |
| | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS |
| | INSTALLATION OR MODIFICATION OF SYSTEM. |
| | IF THERE IS AN EXISTING SYSTEM, THE BTU LOAD OF THE |
| | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FBCR SECS.G2412.4, G2412.8, |
| | G2413.1, G2413.2, G2413.3. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |