| 2018-09-14 18:13:17 | SIGN SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- A) PROVIDE SIGNED AND SEALED DRAWINGS (2 COPIES) |
| | WITH COMPLETE DESIGN CRITERIA INCLUDING THE CURRENT |
| | BUILDING CODE, ULTIMATE DESIGN WIND SPEED AND NOMINAL |
| | DESIGN WIND SPEED, WIND EXPOSURE, RISK CATEGORY AND |
| | DESIGN WIND PRESSURES. AS REQUIRED BY SEC. 1603.1.4 |
| | FBC. |
| | |
| | RESPONSE: |
| | ENGINEER OF RECORD NEED TO PROVIDE ORIGINAL SEAL AND |
| | SIGNATURE ON ALL DRAWINGS AS REQUIRED BY SEC. |
| | 61G15-23.003 FAC. DRAWINGS SUBMITTED HAVE A DIGITAL |
| | SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL. NEED TO |
| | PROVIDE COPIES OF DRAWINGS WITH ORIGINAL SEAL AND |
| | SIGNATURE. |
| | |
| | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND |
| | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN |
| | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, |
| | F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY |
| | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | RULEMAKING AUTHORITY 471.025(1), 668.006 FS. LAW |
| | IMPLEMENTED 471.025 FS. HISTORY?NEW 8-18-98, AMENDED |
| | 9-4-05, 5-6-09, 1-5-12, 8-20-12, 12-10-13, 11-3-15. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |