| 2018-09-13 16:01:27 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18080759 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. NO REVISIONS ARE SHOWN ON PLAN. IT APPEARS THAT AN |
| | EXISTING BATHTUB IN THE MASTER BATH IS BEING REPLACED |
| | BY A NEW LAVATORY AND THAT THE KITCHEN SINK HAS BEEN |
| | RELOCATED. THIS AND ANY OTHER CHANGES NEED TO BE |
| | CLARIFIED ON BOTH A.1.02 AND P.1.01. PROVIDE |
| | DESCRIPTION OF REVISION REQUESTED AND CLOUD CHANGES ON |
| | PLAN. WPB FBC 107.2.1 PROVIDE SANITARY ISOMETRIC FOR |
| | NEW PLUMBING WORK, DETAILING FIXTURE DRAINS, TRAPS, |
| | VENTS, CONNECTIONS TO EXISTING AND SIZING SHOWING |
| | COMPLIANCE WITH FPC CHAPTERS 7 AND 9 PER FBC WPB AMEND |
| | 107.3.5.1.3 |
| | 2. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED |
| | PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE |
| | TYPES WITH HIGH TEMPERATURE LIMITING STOP. FPC 424.3 |
| | 3. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS |
| | 471, 481 |
| | 4. PROVIDE DESCRIPTION OF PIPING MATERIAL PENETRATING |
| | THE FLOOR, OR ANY OTHER RATED ASSEMBLIES (SUCH AS A |
| | MECHANICAL CHASE) AND PROVIDE FIRE STOPPING DETAIL(S) |
| | FOR SAID RATED ASSEMBLIES. ADDITIONALLY PROVIDE |
| | FIRESTOP ASSEMBLY FOR REMOVED BATHTUB WASTE FLOOR |
| | PENETRATION. WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |