| Plan Review Notes For Permit 18080725 |
| Permit Number |
18080725 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-08-27 18:59:55 | RESIDENTIAL (R3) REROOF, THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R4 | | | SUBMITTED: SELECTED INSULATED ASSEMBLY W-2 CAN NOT BE | | | USED FOR ROOF ZONE #3. IT SAYS "N/A" (NOT APPLICABLE). | | | NEED TO SELECTED ANOTHER ASSEMBLY THAT MEETS THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES. SEC. R301.1 | | | FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|