2018-10-01 09:01:15****CORRECTIONS****
 W.P.B. PERMIT: 18080708
 REVIEWED: SEPTEMBER 28, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC AMENDED R107.2.5]SHEET A1 DATA. THE USE TYPE
 WOULDN?T BE R-2, BUT IT SHOULD BE GROUP U PRIVATE
 GARAGE. ALSO, CHECK CONSTRUCTION TYPE III. WALLS WILL
 HAVE WOOD FURRING IN THEM, SO TYPE VB MAY BE
 APPROPRIATE. PLEASE USE FBC TABLE 601 TO CHOOSE
 CONSTUCTION TYPE AND INCLUDE A OR B IN THE TYPE BEING
 UTILIZED.
  
 2. [FBC R404.1.6] CONCRETE AND MASONRY FOUNDATION WALLS
 SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS.
  
 3. [FBC R403.1.4]MINIMUM DEPTH.
 EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
 WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO
 CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2.
  
 4. [FBC R402.4]AIR LEAKAGE (MANDATORY).THE GARAGE DOOR
 WILL BE A BREAK IN THERMAL ENVELOPE. IS THIS DOOR GOING
 TO BE INSULATED? HOW DOES THE GARAGE DOOR MEET
 REQUIRMENTS FOR THERMAL ENVELOPE APPROACH?
  
 5. [FBC TABLE R402.1.2]WHAT IS THE SHGC OF THE GLASS IN
 THE ALUMINUM OUTSWING DOOR? IS THE GLASS INSULATED?
  
 6. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  