| 2018-08-28 06:08:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLEASE PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED |
| | AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED |
| | BY THE ELECTRICAL CONTRACTOR QUALIFIER. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5 |
| | |
| | 2. PLEASE PROVIDE SUBMITTALS FOR PRODUCT APPROVAL OF |
| | ELECTRIC ROLL UP SHUTTER SYSTEM. THE DOCUMENTS PROVIDED |
| | DID NOT SHOW APPROVAL FROM A NATIONALLY RECOGNIZED |
| | TESTING LABRATORY (NRTL) SUCH AS UL, CSA, ETL, ETC. NEC |
| | 110.3B |
| | |
| | 3. LICENSED ELECTRICIAN REQUIRED FOR INSTALLATION OF |
| | ELECTRIC ROLL UP SHUTTER. F.S.489.505 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |