Plan Review Notes
Plan Review Notes For Permit 18080685
Permit Number 18080685
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-08-23 10:36:37THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) LIFE SAFETY SHEET - THERE IS AN INCORRECT EDITION
 YEAR, 2012, INDICATED FOR NFPA 101.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 PLEASE UPDATE YOUR RECORDS AND REFERENCES ON FUTURE
 SUBMITTALS.
  
  
  
 2) ALL FIRE AALARM AND FIRE SPRINKLER WORK SHALL BE
 SUBMITED UNDER SEPARATE SHOP DRAWINGS.
  
  
  