| 2018-08-15 09:13:06 | RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- THE APPLICATION STATUS OF THE PRODUCT APPROVAL FOR |
| | ROOF TILE UNDERLAYMENT FL14317-R9 SUBMITTED IS NOT |
| | APPROVED. IT SAYS PENDING FBC APPROVAL. NEED TO PROVIDE |
| | PRODUCT APPROVAL THAT IS APPROVED (2 COPIES). FAC |
| | 61G20-3.001. |
| | |
| | 2- ROOF TILE UNDERLAYMENT SUBMITTED FOR ADHESIVE |
| | APPLICATIONS: CLEARLY MARK WHICH SPECIFIC UNDERLAYMENT |
| | TYPE AND UNDERLAYMENT SYSTEM IS GOING TO BE USED TO |
| | VERIFY COMPLIANCE WITH THE WIND LOADS SEC. R301.1 |
| | FBC-RESIDENTIAL. NOTE: SEE SEC. 5.6.4 OF FLORIDA |
| | PRODUCT APPROVAL SUBMITTED AND CLEARLY IDENTIFY |
| | UNDERLAYMENT SYSTEM TO BE USED. IF USING THE FRSA/TRI |
| | INSTALLATION MANUAL, THEN PROVIDE APPLICABLE TABLES AND |
| | CLEARLY MARK PROPOSED INSTALLATION AS REQUIRED BY CITY |
| | POLICY FOR ALL ROOFING PERMITS. |
| | |
| | 3- PERMIT APPLICATION SPECIFIES THAT THIS IS A ONE |
| | STORY HOUSE. THIS IS INCORRECT. THIS IS A TWO STORY |
| | HOUSE. PROVIDE THE CORRECT MEAN ROOF HEIGHT FOR PROPER |
| | EVALUATION OF THE WIND LOADS. SEC. R301.1 |
| | FBC-RESIDENTIAL AND CITY POLICY FOR ALL ROOFING |
| | PERMITS. |
| | |