Plan Review Notes
Plan Review Notes For Permit 18080669
Permit Number 18080669
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-30 17:59:5108/30/2018 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN, GAS POOL HEATER AND THE PUMP. WPB AMENDMENTS TO
 FBC SEC. 107.2.1..
 2. SUBMIT SPECIFICATIONS FOR THE CARTRIDGE FILTER. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN AND THE PUMP. WPB AMENDMENTS TO FBC SEC. 107.2.1.
 4. ALL GAS HEATERS SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON OR AFTER
 APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH ANSI Z
 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS SHALL
 NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. 2017
 FBC-ENERGY - SEC. R403.10.4
 5. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC-
 ENERGY- SEC. R 403.10.3.
 6. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A
 LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE
 USED IF NO POOL FILL IS INSTALLED AT THE METER AND
 INSTALLED BY UTILITIES WHICH DOES NOT REQUIRE A PERMIT
 SO PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240
 FOR FURTHER DIRECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  