| 2018-09-21 08:26:59 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18080664 | | | REVIEWED: SEPTEMBER 21, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC ENERGY = FBC ENERGY CONSERVATION | | | | | | PLEASE CO-ORDINATE ELEVATIONS BETWEEN ARCHITECTURAL AND | | | CIVIL. ORIGINAL CIVIL PLANS ARE IN NVGD29 AND SHOW THE | | | F.F.E. AT 18.00. THE REVISION HERE SHOWS THE F.F.E. AT | | | NAVD 18.00. THERE IS A 1.55 MOIFIER BETWEEN THE TWO. | | | ALSO, ORIGINAL CIVIL SUBMITTED WITH GUARDHOUSE PERMIT | | | 16110574 SHOWS F.F.E. AT 18.00 THEN STEP DOWN TO 17.50 | | | FOR SIDE WALK AND STREET LEVEL IS 17.00. IF YOU NOW | | | HAVE F.F.E INTERIOR AND EXTERIOS SIDEWALK AT 18.00 THE | | | STREET WOULD BE AT 17.50. PLEASE PROVIDE UPDATED CIVIL | | | TO ACCOUNT FOR ELEVATION CHANGES. | | | | | | I WILL SEND TWO CLIPS OF ORIGINAL CIVIL PLANS VIA | | | E-MAIL FROM 16110574 TO ERIKA OLIVO TO HELP CLARIFY. | | | | | | | | | | | | | | | | | | |
|