| Plan Review Notes For Permit 18080655 |
| Permit Number |
18080655 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2019-03-29 17:09:33 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY E.I., BN, PX | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 5TH REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | SEE PREVIOUS LIST. NO NEW DOCUMENTS WERE SUBMITTED FOR | | | THIS REVIEW. | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | | | 1. THE INFORMATION PROVIDED ON THE SCHEDULE FOR | | | INSTALLATION OF OPENING PROTECTIVE DEVICES, SHOWS THE | | | SHUTTERS IN A HORIZONTAL SPAN, THIS SHOULD BE IN A | | | VERTICAL AS PER THE IDENTIFIED DETAILS IN THE PRODUCT | | | APPROVAL. | | | | | | | | | 2. SEVERAL DOCUMENTS WERE SUBMITTED MULTIPLE TIMES. FOR | | | EXAMPLE; DESIGN PRESSURE PAGE WAS UPLOADED TWICE, FLOOR | | | PLAN TWICE, TWO DIFFERENT FILES FOR THE INSTALLATION | | | SCHEDULE. PLEASE REFER TO THE PROJECTDOX NAMING | | | CONVENTION OR, IN THE FUTURE, SUBMIT PAPER RATHER THAN | | | DIGITAL. | | | |
|