| Date |
Text |
| 2018-08-16 16:57:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INCORRECT REFERENCE (2009) AND CODE |
| | SECTIONS INDICATED ON THE PLAN SHEET UNDER SYSTEM |
| | COMPLIANCE NOTES. |
| | |
| | PER THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE |
| | THE CORRECT 17 A CODE REFERENCE IS: |
| | |
| | NFPA 17A, STANDARD FOR WET CHEMICAL EXTINGUISHING |
| | SYSTEMS, 2013 EDITION. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT THE EDITION AND THE CODE |
| | SECTIONS THAT ARE INSERTED. |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATIONS THAT THE SYSTEM IS TIED INTO |
| | THE BUILDINGS' FIRE ALARM SYSTEM. |
| | |
| | PER NFPA 17 A |
| | |
| | 5.2.1.9 THE EXTINGUISHING SYSTEM SHALL BE CONNECTED TO |
| | THE |
| | FIRE ALARM SYSTEM, IF PROVIDED, IN ACCORDANCE WITH THE |
| | REQUIREMENTS |
| | OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, SO |
| | THAT THE ACTUATION OF THE EXTINGUISHING SYSTEM WILL |
| | SOUND THE |
| | FIRE ALARM. |
| | |
| | ADDITIONALLY, |
| | |
| | PER NFPA 1 |
| | |
| | 13.7.1.2* BUILDING FIRE ALARM SYSTEMS. PROTECTED |
| | PREMISES FIRE |
| | ALARM SYSTEMS THAT SERVE THE GENERAL FIRE ALARM NEEDS |
| | OF A |
| | BUILDING OR BUILDINGS SHALL INCLUDE ONE OR MORE OF THE |
| | FOLLOWING |
| | SYSTEMS OR FUNCTIONS: |
| | (1) MANUAL FIRE ALARM SIGNAL INITIATION |
| | (2) AUTOMATIC FIRE ALARM AND SUPERVISORY SIGNAL |
| | INITIATION |
| | (3) MONITORING OF ABNORMAL CONDITIONS IN FIRE |
| | SUPPRESSION |
| | SYSTEMS |
| | (4) ACTIVATION OF FIRE SUPPRESSION SYSTEMS |
| | |
| | PER NFPA 101 |
| | |
| | 9.6.2 SIGNAL INITIATION. |
| | 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, |
| | ACTUATION |
| | OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF |
| | THE FOLLOWING |
| | MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH |
| | MEANS: |
| | (1) MANUAL FIRE ALARM INITIATION |
| | (2) AUTOMATIC DETECTION |
| | (3) EXTINGUISHING SYSTEM OPERATION |
| | |
| | PER NFPA 96 |
| | |
| | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING |
| | THE OCCUPANCY |
| | WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE |
| | ACTIVATION |
| | OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL |
| | ACTIVATE |
| | THE FIRE ALARM SIGNALING SYSTEM. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT FOR FIRE ALARM ACTIVATION OR |
| | JUSTIFY WITH SPECIFIC CODE REFERENCES |
| | |
| | |
| | |
| | |
| | 3) THERE IS NO CLEAR INDICATION OF THE LOCATION OF THE |
| | MANUAL ACTPULL STATION. |
| | |
| | 5.2.1.10* A READILY ACCESSIBLE MEANS FOR MANUAL |
| | ACTUATION |
| | SHALL BE LOCATED IN A PATH OF EGRESS. |
| | 5.2.1.10.1 WHEN MANUAL ACTUATION IS USED FOR |
| | COOKINGRELATED |
| | PROTECTION, THE MANUAL ACTUATION DEVICE SHALL BE |
| | INSTALLED |
| | NO MORE THAN 48 IN. (1200 MM) AND NO LESS THAN 42 IN. |
| | (1067 MM) ABOVE THE FLOOR. |
| | 5.2.1.10.2 THE MANUAL ACTUATION DEVICE SHALL CLEARLY |
| | IDENTIFY |
| | THE HAZARD PROTECTED. |
| | 5.2.1.11 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE |
| | LOCATED IN |
| | ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION |
| | CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS, OR AS |
| | DIRECTED BY THE |
| | AUTHORITY HAVING JURISDICTION, WITHIN THE LIMITATIONS |
| | OF THE MANUFACTURER?S |
| | DESIGN, INSTALLATION, AND MAINTENANCE MANUAL. |
| | |
| | 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION |
| | SHALL |
| | BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. AND 48 |
| | IN.) |
| | ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT OF A FIRE, |
| | BE LOCATED |
| | IN A PATH OF EGRESS, AND CLEARLY IDENTIFY THE HAZARD |
| | PROTECTED. |
| | 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE |
| | LOCATED |
| | A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT) |
| | FROM |
| | THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH OF |
| | EGRESS |
| | OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ. |
| | 10.5.1.2 MANUAL ACTIVATION USING A CABLE-OPERATED PULL |
| | STATION |
| | SHALL NOT REQUIRE MORE THAN 178 N (40 LB) OF FORCE, |
| | WITH A |
| | PULL MOVEMENT NOT TO EXCEED 356 MM (14 IN.) TO ACTIVATE |
| | THE |
| | AUTOMATIC FIRE-EXTINGUISHING EQUIPMENT. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE FOR THE ACURATE LOCATION. |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |