| Date |
Text |
| 2018-08-13 16:29:31 | 08/13/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE PROVIDE THE SIZE AND DOCUMENTATION THAT THE |
| | PROPOSED DEVICE IS LEAD-FREE. ALL BACKFLOW DEVICES MUST |
| | BE LEAD FREE. LEAD FREE (LF) SHALL BE INCLUDED IN THE |
| | SERIAL NUMBER OR STAMPED ON THE BODY OF THE DEVICE. ANY |
| | DEVICE THAT HAS BEEN ALTERED AFTER BEING ASSEMBLED BY |
| | THE MANUFACTURER WILL NOT BE APPROVED. |
| | |
| | 2. PLEASE PROVIDE TWO COPIES OF DOCUMENTATION THAT THE |
| | PROPOSED BACKFLOW DEVICE IS ON THE APPROVED DEVICE LIST |
| | PUBLISHED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA |
| | (USC). PLEASE CONTACT DEPARTMENT OF PUBLIC UTILITY |
| | FIELD CUSTOMER SERVICE AT 561-822-2240 FOR DOCUMENTED |
| | CONFIRMATION THAT THE PROPOSED BACKFLOW PREVENTION |
| | DEVICE COMPLIES WITH CITY REQUIREMENTS. |
| | |
| | 3. A DOUBLE CHECK DETECTOR ASSEMBLIES IS REQUIRED FOR |
| | THIS TYPE OF DEVICE ACCORDING TO THE CROSS CONNECTION |
| | CONTROL MANUAL FROM THE CITY OF WEST PALM BEACH. REFER |
| | TO TABLE 1.1, PAGE 15 UNDER CATEGORY OF CUSTOMER. HTTP: |
| | //WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIO |
| | NS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL . |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |