| Plan Review Notes For Permit 18080552 |
| Permit Number |
18080552 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-23 10:24:01 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER DIAGRAM SHOWS TWO ATS??? | | | | | | PLEASE SHOW CLEARANCES AROUND GENERATOR AT SIDE OF | | | HOUSE, WHICH MEET THE MANUFACTURERS RECOMENDATIONS. | | | | | | PLANS NEED TO BE SIGNED. | | | | | | NEED PAD DETAILS. | | | | | | VALUE TO LOW FOR 22K GENERATOR. MUST INCLUDE LABOR | | | ESTIMATES AND ALL MATERIALS. ($750 PER KW IS WHAT WE | | | USUALLY SEE) |
|