| 2018-08-20 09:19:32 | | | | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF GENERATOR PAD DETAILS. SPECIFY | | | HOW THE GENERATOR WILL BE ATTACHED TO THE PAD IN ORDER | | | TO RESIST WINDLOADS. PROVIDE DETAILS SUCH AS PAD | | | DIMENSIONS, REINFORCING, ANCHORING FASTENER TYPES, | | | SIZES, EMBED DEPTH, NUMBER AND LOCATIONS. FBC-R 301.2.1 | | | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. |
|