Date Text
2018-09-18 14:59:331ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080548
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET ME.1
 A. PER FBC WPB AMEND 107.3.5.3 (12), PROVIDE SANITARY
 RISER DIAGRAM FOR 2" WASHER DRAIN PIPE SHOWING THE TRAP
 TO VENT IN ACCORDANCE WITH FBC RES P3105.1, VENT SIZED
 IN ACCCORDANCE WITH FBC RES P3113.1 TO THE OUTSIDE IN
 ACCORDANCE WITH FBC RES P3102.1 AND CONNECTION TO
 EXISTING SANITARY SEWER USING A COMPLIANT FITTING SUCH
 AS A WYE OR COMBINATION WYE AND 1/8 BEND IN ACCORDANCE
 WITH FBC PLUMBING TABLE 706.3 PER FBC RES P2601.1.
 B. PROVIDE NOTE "ACCESSIBLE SHUTOFF VALVES REQUIRED"
 PER FBC RES P2903.9.3.
 C. PROVIDE NOTE "PROVIDE WATER HAMMER ARRESTORS " PER
 FBC RES P2903.5.
 2. PLUMBING SCOPE ON PLAN CALLS ONLY TO FURNISH
 HOT,COLD WATER AND DRAIN FOR NEW WASHER. IF A NEW WATER
 HEATER IS REQUIRED TO ACCOMPLISH THE HOT WATER
 REQUIREMENTS IT WILL NEED TO BE ADDED TO THE PLANS ON
 THE RESUBMITTAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715