| Plan Review Notes For Permit 18080548 |
| Permit Number |
18080548 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-18 14:59:33 | 1ST REVIEW: FBC 2017 6TH EDITION | | | PERMIT 18080548 | | | PLUMBING COMMENTS: DENIED | | | | | | 1. RE: PLAN SHEET ME.1 | | | A. PER FBC WPB AMEND 107.3.5.3 (12), PROVIDE SANITARY | | | RISER DIAGRAM FOR 2" WASHER DRAIN PIPE SHOWING THE TRAP | | | TO VENT IN ACCORDANCE WITH FBC RES P3105.1, VENT SIZED | | | IN ACCCORDANCE WITH FBC RES P3113.1 TO THE OUTSIDE IN | | | ACCORDANCE WITH FBC RES P3102.1 AND CONNECTION TO | | | EXISTING SANITARY SEWER USING A COMPLIANT FITTING SUCH | | | AS A WYE OR COMBINATION WYE AND 1/8 BEND IN ACCORDANCE | | | WITH FBC PLUMBING TABLE 706.3 PER FBC RES P2601.1. | | | B. PROVIDE NOTE "ACCESSIBLE SHUTOFF VALVES REQUIRED" | | | PER FBC RES P2903.9.3. | | | C. PROVIDE NOTE "PROVIDE WATER HAMMER ARRESTORS " PER | | | FBC RES P2903.5. | | | 2. PLUMBING SCOPE ON PLAN CALLS ONLY TO FURNISH | | | HOT,COLD WATER AND DRAIN FOR NEW WASHER. IF A NEW WATER | | | HEATER IS REQUIRED TO ACCOMPLISH THE HOT WATER | | | REQUIREMENTS IT WILL NEED TO BE ADDED TO THE PLANS ON | | | THE RESUBMITTAL. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6715 |
|