| 2018-09-27 12:59:29 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SOILS REPORT - |
| | A. PROVIDE TWO COPIES OF ALL SUBMITTAL DOCUMENTS. |
| | B. ENGINEER'S SIGNATURE AND SEAL TO BE ORIGINAL. |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| | 61G15-23.001. |
| | |
| | 2. PROVIDE SITE DRAINAGE PLAN - |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| | COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. |
| | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| | INCHES WITHIN THE FIRST 10 FEET. |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10 |
| | FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE |
| | DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING |
| | FOUNDATION SHALL BE SLOPED A MINIMUM OF |
| | 2 PERCENT AWAY FROM THE BUILDING. |
| | FBC R 401.3 (DRAINAGE) |
| | FBC 107.2.5 (SITE PLAN) |
| | FBC 110.9 (IMPACT OF CONSTRUCTION) |
| | |
| | 3. ROOFING PERMIT IS REQUIRED - |
| | A. SUBMITTAL NOA 17-1120.01 IS DIFFERENT THAN THA NOA |
| | 11-0307.04 LISTED ON PLAN. PLEASE CLARIFY. |
| | B. SUBMITTAL'S SHALL BE REVIEWED AND APPROVED INWRITING |
| | BY DESIGNER. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. |
| | |
| | 5. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED. |
| | PLEASE SEE COMMENTS UNDER IMPACT REVIEW. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE DOOR SUBMITTALS. |
| | |
| | |