Plan Review Notes
Plan Review Notes For Permit 18080513
Permit Number 18080513
Review Stop P
Sequence Number 2
Notes
Date Text
2018-12-11 15:42:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW: DENIED
  
 1. SECOND REQUEST; PROVIDE SCHEDULE OF OCCUPANCY TYPE
 NOTING OCCUPANT LOAD PER FBC 1004 AND DETERMINE
 COMPLIANCE WITH MINIMUM PLUMBING FACILITIES PER FPC
 403.1 AND TABLE 403.1.
 2. RE P-2; DETAIL-TYPICAL 3 COMPARTMENT SINK. SINK IS
 USED FOR FOOD PREP. EACH COMPARTMENT SHALL DISCHARGE
 INDEPENDENTLY TO FLOOR SINK THROUGH AN AIR GAP. FPC
 802.1.1. REVISE DETAIL TO COMPLY PER FBC WPB 107.2.1.
 3. RE: PLAN SHEET P-2;
 2ND REQUEST. HIGH TEMP KITCHEN WATER DETAIL SHOWING
 COLD WATER CONNECTION TO HIGH TEMP EFFLUENT. IF THIS IS
 A PHYSICAL CONDITION OF THE FACILITY THEN PROVIDE THE
 FOLLOWING PER WPB FBC 107.2.1:
 A. IDENTIFY THE HIGH TEMPERATURE EFFLUENT ON THE
 SANITARY RISER DIAGRAM
 B. PROVIDE EFFLUENT PIPING MATERIAL SPEC RATED FOR HIGH
 TEMP AND COMPLIANT WITH FBC PL CHAPTER 7
 C. SHOW IT ON THE WATER DISTRIBUTION PLAN WITH A HIGH
 HAZARD RPZ BACKFLOW PREVENTER AND INCLUDE IN DETAIL.
 FPC 608.1.
 IF NOT, THEN REMOVE DETAIL FROM PLAN. FBC WPB AMEND
 107.2.1
 4. RE: P-1; AIR GAP FOR DISCHARGE FROM BACKFLOW
 PREVENTER SHALL BE AT THE BACKFLOW PREVENTER WITH AN
 APPROVED AIR GAP FITTING. THE AIR GAP AS NOTED ON THE
 PLANS IS SUBJECT TO COMPROMISE AND COULD POSSIBLY BE
 SUBMERGED. CHANGE NOTE ON FLOOR PLAN AND THE RISER
 DIAGRAM TO REQUIRE AN AIR GAP FITTING AT THE BFP PER
 WPB FBC 107.2.1.
 5. RE: PLAN SHEET P-1; TANKLESS WATER HEATER DETAIL
 APPEARS TO HAVE NOTES WHICH ARE NOT LEGIBLE. PLEASE
 CLARIFY PER WPB FBC 107.2.1.
 6. RE: PLAN SHEET P-2; GENERAL PLUMBING NOTES. THE BULK
 OF THE COMMENTS IS NOT LEGIBLE. PLEASE CLARIFY PER WPB
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715