| 2018-12-11 15:42:21 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW: DENIED |
| | |
| | 1. SECOND REQUEST; PROVIDE SCHEDULE OF OCCUPANCY TYPE |
| | NOTING OCCUPANT LOAD PER FBC 1004 AND DETERMINE |
| | COMPLIANCE WITH MINIMUM PLUMBING FACILITIES PER FPC |
| | 403.1 AND TABLE 403.1. |
| | 2. RE P-2; DETAIL-TYPICAL 3 COMPARTMENT SINK. SINK IS |
| | USED FOR FOOD PREP. EACH COMPARTMENT SHALL DISCHARGE |
| | INDEPENDENTLY TO FLOOR SINK THROUGH AN AIR GAP. FPC |
| | 802.1.1. REVISE DETAIL TO COMPLY PER FBC WPB 107.2.1. |
| | 3. RE: PLAN SHEET P-2; |
| | 2ND REQUEST. HIGH TEMP KITCHEN WATER DETAIL SHOWING |
| | COLD WATER CONNECTION TO HIGH TEMP EFFLUENT. IF THIS IS |
| | A PHYSICAL CONDITION OF THE FACILITY THEN PROVIDE THE |
| | FOLLOWING PER WPB FBC 107.2.1: |
| | A. IDENTIFY THE HIGH TEMPERATURE EFFLUENT ON THE |
| | SANITARY RISER DIAGRAM |
| | B. PROVIDE EFFLUENT PIPING MATERIAL SPEC RATED FOR HIGH |
| | TEMP AND COMPLIANT WITH FBC PL CHAPTER 7 |
| | C. SHOW IT ON THE WATER DISTRIBUTION PLAN WITH A HIGH |
| | HAZARD RPZ BACKFLOW PREVENTER AND INCLUDE IN DETAIL. |
| | FPC 608.1. |
| | IF NOT, THEN REMOVE DETAIL FROM PLAN. FBC WPB AMEND |
| | 107.2.1 |
| | 4. RE: P-1; AIR GAP FOR DISCHARGE FROM BACKFLOW |
| | PREVENTER SHALL BE AT THE BACKFLOW PREVENTER WITH AN |
| | APPROVED AIR GAP FITTING. THE AIR GAP AS NOTED ON THE |
| | PLANS IS SUBJECT TO COMPROMISE AND COULD POSSIBLY BE |
| | SUBMERGED. CHANGE NOTE ON FLOOR PLAN AND THE RISER |
| | DIAGRAM TO REQUIRE AN AIR GAP FITTING AT THE BFP PER |
| | WPB FBC 107.2.1. |
| | 5. RE: PLAN SHEET P-1; TANKLESS WATER HEATER DETAIL |
| | APPEARS TO HAVE NOTES WHICH ARE NOT LEGIBLE. PLEASE |
| | CLARIFY PER WPB FBC 107.2.1. |
| | 6. RE: PLAN SHEET P-2; GENERAL PLUMBING NOTES. THE BULK |
| | OF THE COMMENTS IS NOT LEGIBLE. PLEASE CLARIFY PER WPB |
| | FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |