| 2018-09-12 07:04:59 | REVIEW COMPLETED BY JERALD SMITH 0017-P |
| 2018-09-11 16:40:07 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 180513 |
| | PLUMBING COMMENTS: |
| | |
| | 1. RE: PLAN SHEET P-1; DETAIL 1 AND DETAIL 2; WATER AND |
| | SANITARY PLANS. FIXTURES AND EQUIPMENT ARE NOT LABELED. |
| | FBC WPB AMEND 107.2.1 |
| | 2. RE: PLAN SHEET P-1; FIXTURE SCHEDULE. NUMERIC TAGS |
| | AND CONNECTION SIZES ARE BARELY DISCERNIBLE. INCREASE |
| | LEGIBILITY. FBC WPB AMEND 107.2.1 |
| | 3. RE: PLAN SHEET P-1; NOTES ARE BARELY DISCERNIBLE. |
| | INCREASE LEGIBILITY. FBC WPB AMEND 107.2.1 |
| | 4. RE: PLAN SHEET P-1; STANDARD PDI-G101 TABLE NOTES |
| | ARE BARELY DISCERNIBLE. INCREASE LEGIBILITY. FBC WPB |
| | AMEND 107.2.1 |
| | 5. RE: PLAN SHEET P-1; GREASE PRODUCTION TABLE NOTES |
| | ARE BARELY DISCERNIBLE. INCREASE LEGIBILITY. FBC WPB |
| | AMEND 107.2.1 |
| | 6. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 05- 1" |
| | WASTE NEEDS TO BE AN INDIRECT WASTE DISCHARGING THROUGH |
| | AN AIR GAP TO A TRAPPED AND VENTED WASTE RECEPTOR. IE. |
| | FLOOR SINK FPC 802.1 |
| | 7. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 08- 3 |
| | COMPARTMENT SINK WASTE NEEDS TO BE AN INDIRECT WASTE |
| | DISCHARGING THROUGH AN AIR GAP TO A TRAPPED AND VENTED |
| | WASTE RECEPTOR. IE. FLOOR SINK FPC 802.1 AND IF USED IN |
| | ACTUAL FOOD HANDLING THEN EACH COMPARTMENT SHALL |
| | DISCHARGE INDEPENDENTLY TO SAID WASTE RECEPTACLE |
| | THROUGH AN AIR GAP. FPC 802.1.1. PROVIDE DETAIL. FBC |
| | WPB AMEND 107.2.1 |
| | 8. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 06- TRAPPED |
| | AND VENTED HAND SINK TO DISCHARGE DOWNSTREAM OF GREASE |
| | INTERCEPTOR. |
| | 9. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 19- PROVIDE |
| | DETAIL AND MANUFACTURER'S INFO FOR SEWAGE PUMP. INCLUDE |
| | VALVING AND SIZING OF DISCHARGE TO EXISTING SANITARY. |
| | SHALL MEET REQUIREMENTS OF FPC 712. FBC WPB AMEND |
| | 107.2.1 |
| | 10. RE: PLAN SHEET P-1; DETAIL 3 NUMERIC TAG 19- |
| | CONDENSER PUMP TO DISCHARGE THROUGH AN AIR GAP TO A |
| | TRAPPED AND VENTED WASTE RECEPTOR. IE. FLOOR SINK FPC |
| | 802.1. PROVIDE DETAIL AND MANUFACTURER'S INFO FOR |
| | CONDENSER PUMP. FBC WPB AMEND 107.2.1 |
| | 11. RE: PLAN SHEET P-2; HIGH TEMP KITCHEN WATER DETAIL |
| | SHOWING COLD WATER CONNECTION TO HIGH TEMP EFFLUENT. IF |
| | THIS IS A PHYSICAL CONDITION OF THE FACILITY THEN SHOW |
| | IT ON THE WATER DISTRIBUTION PLAN WITH A HIGH HAZARD |
| | RPZ BACKFLOW PREVENTOR AND INCLUDE IN DETAIL. FPC |
| | 608.1. IF NOT, THEN REMOVE DETAIL FROM PLAN. FBC WPB |
| | AMEND 107.2.1 |
| | 12. TEMPERED WATER TO BE DELIVERED TO HAND SINK AND |
| | LAVATORY IN ACCORDANCE WITH FPC 416.5 |
| | 13. RE: PLAN SHEET P-1; DETAIL 3; WATER DISTRIBUTION |
| | ISOMETRIC. TAG 07 NOT SHOWN ON ANY SCHEDULE. APPEARS TO |
| | BE A TANKLESS WATER HEATER. PROVIDE SCHEDULE AND |
| | DETAIL. FBC WPB AMEND 107.2.1 |
| | 14. RE: PLAN SHEET P-1; DETAIL 2; SANITARY PLAN. REVISE |
| | PLAN TO CLEARLY SHOW UG PIPING, SEWAGE PUMP DISCHARGE |
| | AND ALL FLOOR SINKS. |
| | 15. RE: PLAN SHEET P-2; DETAIL SHOWING AIR ADMITTANCE |
| | VALVES. IF THIS IS A PHYSICAL CONDITION OF THE FACILITY |
| | THEN SHOW IT ON THE SANITARY ISOMETRIC. IF NOT, THEN |
| | REMOVE DETAIL FROM PLAN. FBC WPB AMEND 107.2.1 |
| | 16. CONFIRM THAT WATER TEMPERATURE TO |
| | UTILITY/UTENSIL/POT CLEANING FIXTURES MEET BOARD OF |
| | HEALTH REQUIREMENTS WITHOUT PRESENTING A HAZARD TO |
| | EMPLOYEES USING THESE ITEMS. |
| | 17. PROVIDE SCHEDULE OF OCCUPANCY TYPE NOTING OCCUPANT |
| | LOAD PER FBC 1004 AND DETERMINE COMPLIANCE WITH MINIMUM |
| | PLUMBING FACILITIES PER FPC 403.1 AND TABLE 403.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6715 |