| 2018-09-04 12:22:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18080513 |
| | 9/4/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE CODE COMPLIANCE DATA ON THE PLANS |
| | INCLUDING THE OCCUPANCY CLASSIFICATION OF THE PROPOSED |
| | NEW TENANT SPACE- FBC B, AND THE LEVEL OF ALTERATION |
| | PER CHAPTER 5 FBC EX. THE NEW TEA SHOP APPEARS TO BE |
| | EITHER A CHANGE OF OCCUPANCY OR A CHANGE OF USE. PLEASE |
| | REFER TO SECTION 1009.1 AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.3.1.1 FBC M. |
| | |
| | 2) SHEET M-1: PLEASE REMOVE THE NOTE INDICATING "NO |
| | MECHANICAL WORK TO BE DONE" BECAUSE IT APPEARS A NEW |
| | EXHAUST FAN WILL BE INSTALLED IN THE TOILET ROOM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |