Plan Review Notes
Plan Review Notes For Permit 18080513
Permit Number 18080513
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-04 12:22:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18080513
 9/4/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CODE COMPLIANCE DATA ON THE PLANS
 INCLUDING THE OCCUPANCY CLASSIFICATION OF THE PROPOSED
 NEW TENANT SPACE- FBC B, AND THE LEVEL OF ALTERATION
 PER CHAPTER 5 FBC EX. THE NEW TEA SHOP APPEARS TO BE
 EITHER A CHANGE OF OCCUPANCY OR A CHANGE OF USE. PLEASE
 REFER TO SECTION 1009.1 AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3.1.1 FBC M.
  
 2) SHEET M-1: PLEASE REMOVE THE NOTE INDICATING "NO
 MECHANICAL WORK TO BE DONE" BECAUSE IT APPEARS A NEW
 EXHAUST FAN WILL BE INSTALLED IN THE TOILET ROOM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  