| Date |
Text |
| 2018-09-18 11:49:36 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18080466 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST PLUMBING. FBC 109.3 |
| | 2. TANKLESS WATER HEATER: 1ST REVIEW: FBC 2017 6TH |
| | EDITION |
| | PERMIT 18080466 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST PLUMBING. FBC 109.3 |
| | 2. TANKLESS WATER HEATER: PROVIDE ON PLUMBING PLAN THE |
| | MANUFACTURER, MODEL AND SPECS FOR TANKLESS WATER |
| | HEATER. CONFIRM THAT MANUFACTURER HAS NOT DESIGNATED |
| | THIS UNIT AS A POINT OF USE UNIT DESIGNED FOR USE WITH |
| | SINGLE FIXTURE AND THAT IT WILL PROVIDE ADEQUATE HOT |
| | WATER FOR THE MASTER BATH FIXTURES IN ACCORDANCE WITH |
| | FBC RES 2903.1 |
| | 3. PROVIDE NOTE: SHOWER CONTROL VALVE(S) SHALL BE |
| | PRESSURE BALANCED PB,THERMOSTATIC MIXING (TM) OR |
| | COMBINATION PB/TM VALVE TYPES WITH HIGH TEMPERATURE |
| | LIMITING STOP. 2017 FBC RES 2708.4 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6715 |