Plan Review Notes
Plan Review Notes For Permit 18080440
Permit Number 18080440
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-22 10:22:411) SUBMIT A FLOOR PLAN FOR THE BATHROOM WHERE THE WORK
 IS BEING PERFORMED. THIS BUILDING WAS BUILT IN
 COMPLIANCE WITH THE FAIR HOUSING ACT AND FULL
 COMPLIANCE MUST BE MAINTAINED.
 2) THE HEIGHT OF THE NEW LAVATORY CABINET BEING
 INSTALLED CANNOT EXCEED 34 INCHES FROM THE FINISH FLOOR
 TO THE TOP OF THE COUNTER PER THE FAIR HOUSING ACT.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATER TO BE REPLACED. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 INSTRUCTIONS FOR THE NEW TUB TO BE INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) THE BATHTUB VALVE SHALL BE EQUIPPED WITH A WATER
 TEMPERATURE LIMITING DEVICE THAT LIMITS THE TEMPERATURE
 OF THE WATER TO 120 DEGREES AND THAT CONFORMS TO ASSE
 1070 PER THE 2017 FBC-PLUMBING SEC.424.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  