| 2019-03-15 16:49:57 | 4TH REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18080413 |
| | 2/4/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENT #3 FROM THE 3RD REVIEW PRINTED BELOW HAS NOT |
| | BEEN ADDRESSED. I HAVE PRINTED THE CODE SECTION BELOW. |
| | PLEASE FORWARD TO THE ARCHITECT OF RECORD. |
| | PLEASE NOTE THAT UNTIL ADEQUATE INFORMATION IS PROVIDED |
| | TO VERIFY COMPLIANCE WITH THE EXCEPTION, A HAZARDOUS |
| | EXHAUST SYSTEM WILL BE REQUIRED, AND DAMPERS ARE |
| | PROHIBITED IN THE EXHAUST DUCT- SECTION 510.7.1 FBC M. |
| | SEE SECTIONS 510.7.3 FOR DUCT ENCLOSURE REQUIREMENT, |
| | AND 510.9 FOR DUCT MATERIALS |
| | |
| | 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND |
| | VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM |
| | COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE |
| | PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN |
| | COMPLIANCE. |
| | |
| | 510.2 WHERE REQUIRED. |
| | |
| | A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER |
| | OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF |
| | HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST |
| | SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE |
| | POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS: |
| | |
| | 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT |
| | IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER |
| | FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED |
| | ROOM TEMPERATURE. |
| | |
| | 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| | RATING OF 4 IS PRESENT IN ANY CONCENTRATION. |
| | |
| | 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| | RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS |
| | EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION |
| | OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY. |
| | |
| | EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1, |
| | EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE |
| | EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A |
| | HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN |
| | CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL |
| | CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION |
| | TOXICITY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |