| 2019-02-04 11:07:16 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18080413 |
| | 2/4/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.2: BASED ON THE SUBMITTED MSDS SHEETS, |
| | STORAGE OF FLAMMABLE LIQUIDS NOT EXCEEDING THE MAXIMUM |
| | ALLOWABLE QUANTITIES WILL OCCUR IN THE LAB WHICH |
| | REQUIRES THE ROOM TO BE DESIGNATED AS A "CONTROL AREA" |
| | - SEE SECTIONS 202 AND 414.2 FBC. THE CONTROL AREA |
| | (LAB) IS REQUIRED TO BE SEPARATED FROM OTHER ROOMS AND |
| | SPACES WITH 1-HR FIRE-RESISTANT RATED CONSTRUCTION- |
| | SECTION 414.2.4 AND TABLE 414.2.2 FBC B. |
| | |
| | 2) M1.1: BECAUSE FIRE-BARRIERS ARE NOW REQUIRED TO |
| | ENCLOSE THE LAB, ALL DUCT PENETRATIONS SHALL BE |
| | PROTECTED WITH FIRE DAMPERS- SECTION 607.5.2 FBC M. |
| | |
| | 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND |
| | VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM |
| | COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE |
| | PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN |
| | COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |