| Plan Review Notes For Permit 18080413 |
| Permit Number |
18080413 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-02-04 14:47:41 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) BASED ON THE INFORMATION THAT WAS SUBMITTED TO | | | ADDRESS THE MECHANICAL COMMENTS, IT APPEARS THAT SOME | | | OF THE MATERIALS THAT WILL BE USED AND STORED IN THE | | | LAB ARE CLASSIFIED AS HAZARDOUS. THE HAZARDOUS | | | MATERIALS IN THIS CASE APPEARS TO BE FLAMABLE LIQUIDS. | | | THE QUANTITY OF THE FLAMABLE LIQUIDS THAT YOU PROVIDED | | | ARE WITHIN THE MAXIMUM ALLOWABLE QUANTITY ALLOWED PER | | | CONTROL AREA. REVISE THE PLANS TO SHOW HOW THE STORAGE | | | AND HANDLING OF THESE HAZARDOUS MATERIALS WILL BE | | | ADDRESSED. FBC 307 & 414 | | | |
|