| 2018-10-24 15:05:00 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18080413 |
| | 10/24/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M0.2: A) REFER TO SECTION 414.1.3 FBC B AND PROVIDE |
| | THE HAZARDOUS MATERIALS CLASSIFICATIONS FOR ALL |
| | CHEMICALS LISTED IN THE SCHEDULE AND SUBMIT MSDS SHEETS |
| | FOR EACH- SEE TABLES 307.1(1) AND 307.1(2). B) SHOW THE |
| | LOCATION OF THE FUME HOOD ON THE PLAN AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- |
| | |
| | 2) M1.1: RECIRCULATION OF AIR FROM THE LAB IS ONLY |
| | PERMITTED WHERE THE RESULTING AIRSTREAM CONSISTS OF NOT |
| | MORE THAN 10 PERCENT AIR RECIRCULATED FORM THE ROOM- |
| | TABLE 403.3.1.1 FOOTNOTE G. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |