| 2018-08-23 16:02:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE FULL RISER DIAGRAM AND SHOW LOCATION ON SITE |
| | PLAN OF MAIN LOCATIONS. ALL MAINS SHOULD BE GROUPED. |
| | NEC 230.72; WPB FBC 107.2.1 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE |
| | MAIN PER ONE OF THE METHODS IN NEC 220. ESTIMATING THE |
| | LOAD BASED ON THE OCP SIZE IS NOT A PERMITTED METHOD, |
| | NOR IS A FUTURE DATA RECORDING. HOW IS IT POSSIBLE TO |
| | DESIGN THE SYSTEM WITHOUT KNOWING THE ACTUAL LOAD? |
| | PROVIDE COMPLIANCE. NEC 220 |
| | 3. PLAN STATES THAT THERE ARE 600 AMP FEEDERS TO |
| | WIREWAY, BUT THEN STATES TO UPGRADE TO COMPLY. THIS |
| | INDICATES THAT THE DESIGN PROFESSIONAL DOES NOT KNOW |
| | WHAT IS THERE. HOW IS IT POSSIBLE TO DESIGN WITHOUT |
| | KNOWING THE ACTUAL CAPACITY OF THE WIRING? PROVIDE |
| | CORRECTION. NEC 215.2, 215.5, 310.15; WPB FBC 107.2.1 |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 5. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 |
| | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 7. PROVIDE THE ESSENTIAL ELECTRICAL SYSTEMS REQUIRED |
| | FOR MEDICAL OFFICE. NEC 517.25, 517.45 |
| | 8. CONDUCTOR KEY NOTE 2 SHOWS AN EQUIPMENT GROUNDING |
| | CONDUCTOR (EGC). IF THIS IS A TAP FROM FPL FEED, AN EGC |
| | IS NOT PERMITTED. PROVIDE CORRECTION. NEC 250.6 |
| | 9. SOME RECEPTACLE OUTLETS ARE SHOWN WITHIN 6 FEET OF A |
| | SINK WITHOUT THE PROPER GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |