| 2018-09-18 18:43:50 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ENERGY EFFICIENCY COMPLIANCE FORM R-405 CONTAINS |
| | SEVERAL ERRORS. PLEASE CORRECT. FBC ENERGY CONSERVATION |
| | R103.3 |
| | |
| | A) THE EXTERIOR WALLS ARE LISTED AS WOOD FRAME (R-11) |
| | AND THE PLANS SHOW CONCRETE BLOCK (R- 4.1). |
| | B) THE EXTERIOR WALLS ARE NOT ALL 8 FEET IN HEIGHT. |
| | ONLY THE NORTH WALL IS 8 FEET IN HEIGHT. SEE PLANS. |
| | C) THE NORTH WALL HAS ONE 10' X 6'-8" SLIDING GLASS |
| | DOOR (WHICH COUNTS AS A WINDOW) AND NOT TWO WINDOWS AS |
| | LISTED ON THE FORM. |
| | D) THE PLANS SPECIFY A TANKLESS WATER HEATER NOT A 40 |
| | GALLON TANK WATER HEATER. |
| | E) THE FORM LISTS NO ATTIC AND ALSO A VENTED ATTIC. |
| | PLEASE CLARIFY. |
| | |
| | 2) PROVIDE A NORTH CARDINAL DIRECTIONAL ARROW ON THE |
| | PLANS THAT INDICATES THE ORIENTATION OF THE STRUCTURE. |
| | FBC 107.2.1 & FBC ENERGY CONSERVATION R405.4.2.1 |
| | |
| | 3) PROVIDE A CROSS SECTION OF THE ENTIRE STRUCTURE THAT |
| | SHOWS A PERPENDICULAR VIEW OF THE ROOF TRUSSES. FBC |
| | 107.2.1 |
| | |
| | 5) SHOW COMPLIANCE WITH FBC-R807 FOR ATTIC ACCESS. |
| | |
| | 6) THE FLOOR PLAN ON SHEET 1 AND THE SLAB, BEAM AND |
| | COLUMN PLAN ON SHEET 02 SPECIFIES A 10' TOP OF BEAM |
| | HEIGHT AT THE FRONT OF THE STRUCTURE. THE ELEVATION |
| | SHOWS A 14' ELEVATION AT THE FRONT OF THE BUILDING. |
| | PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 7) PROVIDE A TRUSS BRACING DETAIL. FBC-R802.10.3 |
| | |
| | 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS AND EXTERIOR EGRESS ENTRY DOOR. |
| | |
| | 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. DUE TO MISSING |
| | INFORMATION FROM THE CONSTRUCTION DOCUMENTS, ADDITIONAL |
| | PLAN REVIEW COMMENTS MAY BE GENERATED DURING PLAN |
| | RESUBMISSION. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |