Plan Review Notes
Plan Review Notes For Permit 18080398
Permit Number 18080398
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-15 15:13:4208/15/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON FORM R405-2017 OF THE FLORIDA ENERGY EFFICIENCY
 CODE HAS A ELECTRIC HEATER EF 0.92 BUT ON YOUR SHEET 02
 IT SHOW A TANKLESS AND ON E-1 IT REFERS IT AS A GAS
 TANKLESS, PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. THE HOME HAS A GAS APPLIANCE, AS FOR THE COOK TOP IT
 HAS A 20 AMP CIRCUIT TO IT, IT?S ON ELECTRICAL LEGEND
 ON PAGE E-1, AND WILL THE COOK TOP BE GAS OR ELECTRIC,
 PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. A SEPARATE PERMIT WILL BE REQUIRED FOR GAS AND A
 REVIEW, WPB AMENDMENTS TO THE FBC SEC. 105.1 REQUIRED
 APPLICATION FOR PERMIT
 4. NO CLEAN OUT REQUIRED AT BASE OF STACK, IF
 PREFERENCE YOU MAY REQUIRE IT BUT NOT IN THE CODE ONLY
 OUTSIDE IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  