| 2018-08-30 12:59:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOAD CALCULATION IS NOT ACCURATE. PROVIDE ACCURATE |
| | LOAD CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE |
| | E3602.2 |
| | |
| | 10KW @100%= 5000KW FOR A/C? |
| | |
| | APPLIANCE (NOT LABLED) 3000KW? |
| | |
| | 2. I AM NOT AWARE OF A COOKTOP UNIT THAT IS 20AMP @ |
| | 1500WATTS. PLEASE PROVIDE UL OR OTHER NRTL LISTING AND |
| | ADJUST LOAD CALC ACCORDINGLY. NEC 110.3B |
| | |
| | 3. JACUZZI TUB RECEPTACLE NEEDS GFCI PROTECTION. |
| | 680.43A3 NEC |
| | |
| | 4. KITCHEN REQUIRES MINIMUM OF 2-20AMP SMALL APPLIANCE |
| | CIRCUITS, ONLY ONE ON PLANS. PLEASE PROVIDE CORRECTION. |
| | 210.52B1 NEC |
| | |
| | 5. SMOKE DETECTOR OUTSIDE OF BEDROOM MUST ALSO BE A |
| | CARBON MONOXIDE DETECTOR. FBC R315.1 |
| | |
| | 6. NO LOCATION FOR SERVICE EQUIPMENT ON PLAN, PLEASE |
| | PROVIDE CORRECTION. FBC 107.2.1 INFORMATIONAL NOTE: |
| | SERVICE RECEPTACLE REQUIRED WITHIN 50' OF SERVICE. |
| | 210.64 NEC |
| | |
| | 7. POWER UTILITY NORMALLY DOESNT INSTALL RIGID STEEL |
| | CONDUIT TO METER, USUALLY IT IS PVC TYPE CONDUIT. |
| | PLEASE CONFIRM WITH POWER UTILITY AND PROVIDE |
| | CORRECTION. FBC 107.2.1 |
| | |
| | 8. DISHWASHER MUST BE ARC-FAULT AND GFCI PROTECTED |
| | 210.8D, 210.12A NEC |
| | |
| | 9. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ANY NEW |
| | OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |