2018-09-04 14:52:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18080384
 9/4/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW 15 TON AC SYSTEMS ARE OVERSIZED. THE
 CALCULATED SENSIBLE LOADS OF 103.6 MBH (RTU-1) AND
 104.4 MBH (RTU-2) INDICATE THAT THE ORIGINAL 12.5 TON
 UNITS WITH CAPACITIES OF 111.5 MBH ARE CAPABLE OF
 HANDLING THE LOADS- SECTION C403.2.2 FBC EC. PLEASE
 NOTE THAT THE SQUARE FOOTAGE CALCULATIONS SHOWN IN THE
 REVISED AC AND ENERGY CALCULATIONS DO NOT MATCH THE
 CALCULATIONS SHOWN IN THE ORIGINAL CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  