| Plan Review Notes For Permit 18080384 |
| Permit Number |
18080384 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-04 14:52:10 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18080384 | | | 9/4/18 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE NEW 15 TON AC SYSTEMS ARE OVERSIZED. THE | | | CALCULATED SENSIBLE LOADS OF 103.6 MBH (RTU-1) AND | | | 104.4 MBH (RTU-2) INDICATE THAT THE ORIGINAL 12.5 TON | | | UNITS WITH CAPACITIES OF 111.5 MBH ARE CAPABLE OF | | | HANDLING THE LOADS- SECTION C403.2.2 FBC EC. PLEASE | | | NOTE THAT THE SQUARE FOOTAGE CALCULATIONS SHOWN IN THE | | | REVISED AC AND ENERGY CALCULATIONS DO NOT MATCH THE | | | CALCULATIONS SHOWN IN THE ORIGINAL CALCULATIONS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|