Plan Review Notes
Plan Review Notes For Permit 18080384
Permit Number 18080384
Review Stop B
Sequence Number 1
Notes
Date Text
2018-09-02 18:07:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THIS ADDRESS HAS SEVERAL EXPIRED PERMITS, INCLUDING
 PERMITS FOR THIS UNIT. WORK IS NOT CONSIDERED
 "EXISTING" UNLESS IT IS PERMITTED, INSPECTED, AND
 FINALED. PLEASE RESOLVE EXPIRED PERMITS.
  
 2. A.1, THE ISSUED PERMIT STATED THIS IS ASSEMBLY, IT
 IS NOW BUSINESS. IS THIS A CHANGE OF OCCUPANCY? IF THIS
 IS A CHANGE OF OCCUPANCY, PLEASE SEE FBC EB CHAPTER 10;
 REVISE PLAN TO SHOW COMPLIANCE WITH ALL REQUIREMENTS.
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 3. A.2, A "PLYWOOD PLATFORM" WAS ADDED IN ROOM 107
 SUPPORT SPACE. SEE FBC A 202.1.1, EITHER PROVIDE
 VERTICAL ACCESSIBLITY OR REVISE PLAN TO SHOW APPLICABLE
 EXCEPTION.
  
 4. A.2, FBC B 1009.15, NO HANDRAILS ARE SHOWN AT THE
 PLYWOOD PLATFORM WHICH HAS TWO RISERS. EITHER ADD
 HANDRAILS OR REVISE PLAN TO INCLUDE APPLICABLE
 EXCEPTION.
  
 5. A.2, FBC A 202.1.1, OPEN OFFICE 101, RAMP WAS
 REMOVED FROM THE PLAN. IT APPEARS THAT VERTICAL
 ACCESSIBLITY IS REQUIRED. SEE ALSO FBC A 202.4, AN
 ACCESSIBLE ROUTE IS REQUIRED.
  
 REVISE TO INCLUDE OR PROVIDE RATIONALE VIA EMAIL PRIOR
 TO RESUBMITTING.
  
 6. FBC 109, VALUE APPEARS LOW. THIS REVISION APPEARS TO
 ADD SEVERAL OFFICES, $2500 VALUE WAS SUBMITTED. PROVIDE
 A COST BREAKDOWN.
  
 7. THE ISSUED PERMIT WAS FOR THE INTERIOR OF SUITE 102.
 THE PLAN REFERRED TO THE SPACE AS "SPACE A". THE
 REVISION NOW LABELS THIS SPACE "101". PLEASE CORRELATE.
 AN ADDRESS STOP HAS BEEN ADDED; PLEASE RESOLVE PRIOR TO
 RESUBMITTING.
  
  